Installation
For appliance installation and use it is necessary to observe all of the local, national and European laws and
regulations.
Stove installation and the preparation of the building work must observe the regulation in force in the country of
installation (ITALY = UNI 10683).
! IMPORTANT
Requirements for the installation premises
The stove installation room must be sufficiently ventilated. To fulfil this requisite it is necessary to equip the room with an air intake
connected to the outdoors.
! IMPORTANT
! IMPORTANT
The stove must be placed inside living quarters. It must never be installed outdoors and in explosive rooms. The volume of the
room where it is installed must be suitable for the power of the appliance and, in any case, greater than 15 m
ATTENTION!
When extraction fans (example: extraction hoods) are used in the same room or space as the stove, this can
cause problems to stove operation.
The stove must be installed on a floor with suitable load capacity. If the existing position does not fulfil this
requirement, it is necessary to take due measures (for example, using a load distribution plate).
ATTENTION!
provide due insulation if the surface is made of flammable material.
If the side walls adjacent to the stove are made of a flammable material, it will be necessary to position the stove at least 30 cm from
them.
Antiwind grille
Flue
Use and maintenance manual RBV 706 - RBV 708
The installation activities must be carried out by a technician that is qualified and/or
authorised by the Manufacturer. The staff in charge of installation must issue a declaration
of conformity of the system to the buyer, whereby they take full responsibility for the final
installation and good operation of the installed product.
Ravelli shall not be held liable if these precautions are not followed.
The installation room must have an air intake with a free cross-section of at least 100
cm
.
2
For installation in the presence of other combustion appliances or VMC system it is
necessary to check the appliance for correct operation.
Minimum clearances from combustible materials
A
B
C
E
Flue connection
Inspection door on
flue
Rev.1 14/02/18
Page 49
EN
.
3
200
221
1000
300