Descargar Imprimir esta página

T.I.P. GPK 3600 Instrucciones Para El Manejo página 14

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 32
The pump must not be used in such locations unless it is set up firmly and flood-proof, a minimum distance of two
metres away from the border of the water body and secured against falling into the water by a solid holding
device. For this purpose the device is to be bolted down firmly to the ground at the fastening points provided
(please refer to the chapter titled "Stationary installation").
6. Electrical conection
The unit is equipped with a mains connection cable and a mains plug. It must only be replaced by qualified staff to
avoid any danger. Please do not use the mains connection cable to carry the pump, and do not use this cable to
pull off the plug from the socket, either. Protect the mains connection cable and mains plug from heat, oil or sharp
edges.
The values stated in the technical details have to correspond to the mains voltage. The person
responsible for the installation has to make sure that the electrical connection is earthed in
compliance with the applicable standards.
The electrical connection has to be equipped with a highly sensitive residual current circuit-
breaker (FI switch): ∆ = 30 mA (DIN VDE 0100-739).
If extension cables are used, their cross-section must not be smaller than that of rubber-
sheathed cables of the H07RN-F (3 x 1.0 mm²) short code. The mains socket and the plug-
and-socket elements have to be in splashwater-proof design.
7. Putting into operation
Please observe the illustrations, too, which are contained as an attachment at the end of the present operating
instructions. The numeric and other details included in brackets below refer to these illustrations.
Prior to putting the pump into operation for the very first time, the pump housing
should be fully vented - i.e. filled with water - even in the case of self-priming
units. If this venting is omitted, the pump will not suck in the liquid to be
discharged. It is highly recommendable, yet not mandatory, to vent the intake
line as well, i.e. to fill it with water.
The pump must only be operated in the performance range indicated on the type plate.
Dry-running - i.e. operating the pump without discharging water - is to be avoided since the
absence of water may cause the pump to run hot. This may cause considerable damage on
the device. Moreover, this means that very hot water will be enclosed within the system so that
there is a hazard of scalding. If the pump has run hot, please pull off the mains plug and allow
the system to cool down.
Please do not expose the pump to moisture (e.g. when operating sprinklers). Do not expose
the unit to rain, either. Make sure that no dripping connections are located above the pump.
The pump should not be used in wet or moist environments. Make sure that the pump and the
electrical plug connections are arranged in a flood-proof place.
The pump must not be running with the feeder line closed.
As long as the device is connected to the electrical mains, one must never reach with one's
hands into the opening of the pump.
Each time the pump is put into operation, please make sure that the pump is set up securely and firmly standing.
The unit must always be positioned upright on an even surface.
Please inspect the pump visually prior to each use. This applies in particular to the mains connection line and the
mains plug. Make sure that all screws are firmly tightened, and verify the perfect condition of all connections. A
damaged pump must not be used. In any case of damage, the pump has to be inspected by qualified service
staff.
Prior to the first time the pump is put into operation, the pump housing (8) has to be fully vented. To do so, please
fill the pump housing (8) through the filling opening (9) completely with water. Please check to make sure that no
leakage occurs. Subsequently, close the filling opening airtight again. It is highly recommended to vent the suction
11
4

Publicidad

loading