PRODUCT FEATURES
The State of Massachusetts requires that the chimney flue damper, when
used with decorative gas log sets, be welded open or completely removed. In the State of
Massachusetts, this appliance must be installed by a licensed plumber or gasfitter.
In the State of Massachusetts the gas cock must be a T-handle type. The State of
Massachusetts requires that a flexible appliance connector cannot exceed three feet
in length.
LOCAL CODES
Install and use log set with care. Follow all codes. In the absence of local codes, use the
latest edition of The National Fuel Gas Code, ANSI Z223.1, also known as NFPA 54*.
*Available from:
American National Standard Institute, Inc.
1430 Broadway
New York, NY 10018
UNPACKING
CAUTION: Do not remove the metal data plates from the burner pan. The data
plates contain important product information.
1. Remove logs, pan materials, and hardware from carton.
2. Remove all protective packaging applied to logs and base for shipment.
3. Check all items for any shipping damage. If damaged, promptly inform GHP Group, Inc.
at 1-877-447-4768.
For Masonry Built
Fireplaces Free Opening
Area Of Chimney Damper
Chimney
Height*
(ft)
6
8
10
15
20
30
Height is from hearth to top of chimney
*
and the minimum height is 6 feet.
** Chart shows minimum opening (sq. in.)
for a given height and input rate.
Log Set Size
18"
24"
30"
M inimum Opening**
(sq. in.)
41.7
49.2
56.6
38.7
45.5
52.4
35.2
41.7
48.2
32.0
37.7
43.2
28.8
34.3
39.8
26.5
31.2
35.9
National Fire Protection Association, Inc.
1 Batterymarch Park
Quincy, MA 02269-9101
Fig. 1
For Factory Built
Fireplaces Free Opening
Area Of Chimney Damper
Chimney
Height*
(ft)
10
15
20
25
30
35
40
* Height is from hearth to top of chimney
and the minimum height is 10 feet.
** Chart shows minimum opening (sq. in.)
for a given height and input rate.
6
Log Set Size
18"
24"
30"
M inimum Opening**
(sq. in.)
28.3
35.3
44.2
21.2
26.4
32.2
18.1
22.1
26.4
15.9
18.1
22.1
14.5
17.3
20.4
13.2
15.9
18.9
12.6
15.2
18.1