20
nl | Technische specificaties
4
Technische specificaties
LSN input voltage
Max. current consumption from LSN
Current consumption when output activated
Output
Max. switched voltage of outputs
Max. output current rating
External power supply
Input
Line monitoring with EOL
EOL resistor
Overall line resistance R
Contact monitoring
Max. current strength (current pulse)
Minimum activation time of the input
Permissible wire diameter
Permissible operating temperature
Permissible storage temperature
Permissible rel. humidity
Protection class as per IEC 60529
Classes of equipment as per IEC 60950
Housing material and color
Dimensions
Weight
2023-07 | 04 | F.01U.032.853
(R
= R
 + R
 + R
)
Σ
Σ 
L/2
L/2
EOL
Installation Guide
15 to 33 V DC
1.9 mA
≤ 2.5 mA
30 V DC
700 mA per output (depending on power supply)
5 to 30 V DC
Nominal 3.9 kΩ
In standby: 1500 to 5500 Ω
Short-circuit: < 800 Ω
Interruption: > 85000 Ω
8 mA
3.2 s
2
0.6 to 2.0 mm
-20 to +65 °C
-25 to +80 °C
< 96 %, non-condensing
IP 30
Class III equipment
ABS/PC blend, signal white (RAL 9003)
Approx. 50 x 22 mm (Ø x H)
Approx. 35 g