Modello - Modèle - Model
Modell - Modelo - Modelo
Fabbricante - Constructeur - Manufacturer
Hersteller - Fabricante - Fabricante
Service manual
IT
FR
EN
EN
DE
ES
For EVCO controllers:
Baud rate: 9600; Slave ID: 247; Parity:
Even
Doc. n° UM000000 | Rev. "B" | 05/07/23
Epta Spa - Via Mecenate, 86 - 20138 Milano (MI) ITALIA
Tel. 02/55403211 Telefax 02/55401023
1
2
1
2
1
2
LINEON
- Once verified, go to the next step.
6) Reboot.
- Disconnect the external power supply.
- Wait one minute and reconnect the
external power supply.
- Login to the platform and check if the
device is online.
- If the device is online, no further action is
required.
- If not, go to the next step.
7) Please return the device to the factory for
further analysis and replace it with a new
one. Use the TMX Provisioning Tool APP to
pair the new gateway with the controller and
the cabinet.
Note: The external antenna can be pur-
chased from Epta.
Antenna type
SAP text
Mobile network
antenna
AC_ANT_03_
(EXT.CELL.ANT)
GPS antenna
ANT. AC_
GPS_03_
(EXT.GPS)
SAP code
TMX
89291000
TMX
89290000
10