NOTICE D'INSTALLATION & D'UTILISATION
Sirène F1V2
Tableau des sons (versions 115 Vca et 230 Vca)
Son 1
Description
1
800/1000 Hz @ 0.25 sec bi ton BS5839 Alarm Tone
2
500/1200 Hz @ 0.3 Hz 0.5 sec Sirène montante NEN 2575:2000
3
Dents de scie 1200/500 Hz @ 1 Hz DIN / PFEER P.T.A.P
4
544Hz (100mS)/440 Hz (400mS) AFNOR NF S 32 001
5
Continu 1000 Hz PFEER toxic gas
6
Cloche
7
Balayage 800/1000 Hz @ 7 Hz
8
Balayage 2400/2900 Hz @ 50 Hz
9
420 Hz @ 0.625 sec
10
500 1200 Hz 3.75 sec / 0.25 sec vacuation Australie
Tableau des sons (version 24Vcc)
Description
Son 1
1
800/1000 Hz @ 0.25 sec bi ton BS5839 Alarm Tone
2
500/1200 Hz @ 0.3 Hz 0.5 sec Sirène montante NEN 2575:2000
3
Dents de scie 1200/500 Hz @ 1 Hz DIN / PFEER P.T.A.P
4
544Hz (100mS)/440 Hz (400mS) AFNOR NF S 32 001
5
Cloche
6
Balayage 800/1000 Hz @ 7 Hz
7
500 1200 Hz 3.75 sec / 0.25 sec vacuation Australie
8
Continu 1000 Hz PFEER gaz toxique
9
Continu 554 Hz
10
420 Hz @ 0.625 sec Alerte Australie
VdS / CPR
Tableau des sons
F1V2 24 Vcc (18-30 Vcc) est conforme CPR
EN54-3
Les sons ci-dessous ont été testés selon EN54-3 et
sont conformes au Règlement Produits de Construc
tion
EN54-3 résultats des essais: Document D0665
Son 1
Description
1
800/1000 Hz @ 0.25 sec bi tonBS5839 Alarm Tone
2
500/1200 Hz @ 0.3 Hz 0.5 sec Sirène montante NEN 2575:2000
3
Dents de scie 1200/500 Hz @ 1 Hz DIN / PFEER P.T.A.P
4
544Hz (100mS)/440 Hz (400mS) AFNOR NF S 32 001
8
Continu 1000 Hz PFEER gaz toxique
9
Continu 554 Hz
ae&t - 4 impasse Joliot Curie - 64110 JURANÇON
99dB(A) @1m
100dB(A) @1m
99dB(A) @1m
97dB(A) @1m
Son No.1
100dB(A) @1m
Son No.2
95dB(A) @1m
99dB(A) @1m
Son No.3
100dB(A) @1m
97dB(A) @1m
Son No.4
100dB(A) @1m
Son No.5
Son No.6
F1V2 dB@ 1m
Son 2
Son No.7
99dB(A) @1m
8
100dB(A) @1m
1
Son No.8*
99dB(A) @1m
8
Son No.9*
97dB(A) @1m
9
95dB(A) @1m
1
Son No.10*
99dB(A) @1m
8
100dB(A) @1m
10
100dB(A) @1m
97dB(A) @1m
97dB(A) @1m
Type B
IP55
F1V2 dB@ 1m
99dB(A) @1m
100dB(A) @1m
99dB(A) @1m
97dB(A) @1m
100dB(A) @1m
97dB(A) @1m
info@aet.fr
aet.fr
Accès au boîtier
CC
CA
* Pour les sons 8, 9 & 10
sur les versions DC,
connecter Alim- à S2
Positions des perçages
Page 2 of 2
Retirer les 2 vis
Ouvert
Voir D242-05-001
Boîtier Sonora
Par défaut: Boîtier Multi-usage
Fixer le joint fourni sur le boitier
arrière afin de garantir le niveau
d'étanchéité
Visser 5Nm
Fermé
D240-00-002-IS Issue 2 01/07/2021