Descargar Imprimir esta página

Ecoflam BLU 20000.1 PR Manual Del Usuario página 13

Quemador de gas progresivos

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 26
LANDIS & STAEFA, Model LFL1.622-1.333 OPERATING CYCLE
Normal operating cycle
Ciclo di funzionamento normale
t2
t1
Gas manostat
Pressostato gas
Motore ventilatore
Fan motor
Pressostato aria
Air Switch
t4
Trasformatore
Ignition transformer
di accensione
Valvola gas
Gas valve
Consenso
Min/max capacity
min./max. potenza
enabling device
100%
Serranda aria
min
Air damper
0
Gas damper
Farfalla gas
Rivelazione
Flame detector
di fiamma
Cut-out pilot lamp
Spia di blocco
the same time the two gas valves open (Vs safety valve and Vl Low flame working valve). The total safety, in case of
missed ignition or casual burner's flame-out, is granted by a ionisation probe which cuts-in and sets the burner shut-
down within the safety time. In case of gas lack or a major pressure drop, the minimum air pressure switch shuts down
the burner.
LANDIS & STAEFA SQM 50.481A2 AIR DAMPER MOTOR
Remove cover to gain access to the adjusting cams.The cams are to be adjusted through the suitable key provided for.
Description:
CALCULATING THE BURNER CAPACITY
To calculate the burner's capacity in kW, proceed as follows: Check the gas flow rate (in liters) on
the counter and the time of the reading in seconds.
Proceed with the calculation using the following :
ignition failureNormal operating cycle
t3
t1
t5
t6
I
- High flame opening position adjusting cam (Air)
II
- Limit switch for the air damper position at burner's shut down
III - Min. flame opening position adjusting cam (Air).
IV - Low flame opening position adjusting cam (Air)
V - Not used cam
Cam VIII
VI - Not used cam
is never used
VII - Not used cam
VIII - Not used cam
e x f = kW
sec
420010310900 BLU 23000.1 - 25000.1 PR TS
Operating cycle in the event of
Ciclo di funzionamento�
in mancanza di fiamma all'accensione
t2
t3
t4
13
Ref. Description
t1
Duration Waiting time for confirmation
t2
of air pressure
t3
Preventilation time
t4
Safety time
t5
Pressurizing time
Time for enabling operation of the
main gas valve on minimum capacity
t6
Time for enabling operation of the
main gas valve on maximum capacity
The control box starts the burner
fan, to carry out the prepurging
of the combustion chamber, and
cheks the vent air pressure throu-
gh the air pressure switch. At the
end of prepurging, the ignition
transformer cuts-in and generates
a spark between the electrodes. At
e
= Litres gas
sec = Time in second
G20 = 34,02
f
G30 = 116
G31 = 88
EN
Duration
8"
66"
2"
4"
10"
10"

Publicidad

loading