6. PROGRAMMATION
IL EST UTILISÉ POUR RÉGLER LE
NOMBRE MAXIMUM DE
DÉMARRAGES DU MOTEUR
DANS UNE HEURE
MAX DEBUTS PAR
HEURE
10
OFF. EXCLUT LE CONTRÔLE
SUR LES DEMARRAGES DES
MOTEURS
MAX DEBUTS PAR
HEURE
OFF
MAX DEBUTS PAR
HEURE
OFF
IL SERT POUR DÉFINIR LE
TEMPS D'ATTENTE DU RÉSEAU
RANGE 1 ÷ 30min
ATTENTE PRESENCE
RESEAU 1min
ATTENTE PRESENCE
RESEAU OFF
OFF EXCLUT L'ATTENTE
PRÉSENCE AU RÉSEAU
ATTENTE PRESENCE
RESEAU OFF
STABLE DÉMARRE LE MOTEUR AVEC
UN PULSE SUR LE BOUTON MAN;
ARRÊTE LE MOTEUR AVEC UN
PULSE SUR LE BOUTON RESET
BOUTON MANUEL
STABLE
INSTABLE DÉMARRE LE MOTEUR
SEULEMENT PENDANT LA
PRESSION SUR LE BOUTON MAN
BOUTON MANUEL
INSTABLE
BOUTON MANUEL
INSTABLE
OFF EXCLUT LE CONTRÔLE
SUR LA TENSION MINIMALE
TENSION MINIMALE
OFF
IL EST UTILISÉ POUR RÉGLER LA
TENSION DE FONCTIONNEMENT
MINIMAL DES MOTEURS
RANGE 180 ÷ 220V (SA694.xx)
RANGE 340 ÷ 380V (SA697.xx)
TENSION MINIMALE
207V
TENSION MINIMALE
207V
15
IL SERT POUR RÉGLER
LE DÉLAI D'ACTIVATION
DE LA SORTIE D'ALARME
RANGE 1 ÷ 250min
DELAI ALARM
DELAI ALARM
OFF EXCLUT LE DÉLAI
DELAI ALARM
OFF EXCLUT LE CONTRÔLE
SUR LA TENSION MAXIMALE
TENSION MINIMALE
IL EST UTILISÉ POUR RÉGLER LA
TENSION DE FONCTIONNEMENT
MAXIMAL DES MOTEURS
RANGE 230 ÷ 253V (SA694.xx)
RANGE 400 ÷ 440V (SA697.xx)
TENSION MAXIMALE
TENSION MAXIMALE
PRESSEZ POUR VOIR LA PARTIE
RESTANTE DE PARAMÈTRES
VOIR CHAPITRE 5.1
PRESSEZ POUR PLUS DE 1S POUR
QUITTER LE SETUP ET ENREGISTRER
LES PARAMÈTRES DANS LA MÉMOIRE
FRANCAISE
1 min
OFF
D'ALARME
OFF
OFF
253V