After appropriate wiring, set the ATS switch to "AUTO" position and the system will be under automatic control.
Therefore, as long as the ATS identifies the existence of power from source 1 (mains voltage), it will light the LED indicator
(mains voltage) and then the LED indicator (AUTO).
This means that the energy flowing for the functioning of the equipment(s) is coming from the mains.
When the ATS identifies the lack of power from source 1 (mains voltage), after stabilising, it will activate source 2
(generator). Then the LED (generator) will light up.
The multicore cable connects the ATS to the generator, allowing the ATS to actuate the pressure regulator, starter, battery
and some other relevant circuits in the generator by switching it on and off.
It may occur that the ATS identifies the lack of mains power supply and although it sends the order to start the generator,
it will not work. In this case, it will make 2 more attempts at 5 second intervals. If the generator still does not start, the LED
indicator (failure) will light up and this means that the generator must be CHECKED, as there is some irregularity, for
example: lack of fuel and/or low oil level.