3-3. Installing the Refrigerant Tubing
The size of the refrigerant tubing is as shown in the table below.
Table 3-1
Type
Gas tube
(Brazing connection)
ø9.52 (Flare connection)
Tightening torque (approximate)
Liquid tube
Thickness of connecting tube
NOT E
To fasten the flare nuts, apply specified torque.
• When brazing, must be cool the pipe by wet cloths after removing the insulation tube and the cover plate.
• When brazing the gas tubing, cool the tubing with dampened shopcloths as you work, as shown in the figure below, to protect the
unit's thermistor from the heat generated by brazing.
• The type 200 indoor unit comes with a tube connector that is for liquid tubing. Configure as shown in the illustration and connect it.
When flaring the tube, put the flare nut onto it first and then flare it.
• Pipe insulation must be made after leak detection for tubing connection area was performed.
• Be sure to insulate both the gas tubing and liquid tubing.
In addition, wrap the supplied insulation material around the tubing joints, and fasten in place with vinyl tape or other means.
Failure to insulate the tubing may result in water leakage from condensation.
• Plug all gaps at tube through-holes in the unit with insulation or a similar substance to prevent air leakage.
200
ø25.4
ø12.7 (Flare connection)
Tightening torque (approximate)
: 34 ~ 42 N • m
Thickness of connecting tube
: 0.8 mm
Gas tubing
Insulation
tube
Longer screw
To outdoor unit
250
ø25.4
(Brazing connection)
: 49 ~ 61 N • m
: 0.8 mm
Cover plate
Remove the ø12.7 flare nut
from the liquid tubing of the
indoor unit and use it.
To indoor unit
Flare the
tubing
Tube connector for
Braze
ø 9.52
200 type (Accessory)
8
Dampened
shopcloths
(wet cloths)