MAPAS DEL REGISTRO MODBUS
INPUT REGISTERS
1
Temperature reading
2
Output value 1 (T)
3
Temperature alert flag
Temperature range
4
limit flag
Humidity, temperature
5
sensor fault
6
Temperature reading 2
Wall temperature alert
7
flag
Wall temperature range
8
limit flag
Wall Temperature
9
sensor fault
10
Relative humidity level
11
Output value 2 (rH)
Relative humidity alert
12
flag
Relative humidity range
13
limit flag
Humidity, temperature
14
sensor fault
15
Dew point level
16—40
41
Ambient light intensity
42
Active / Standby
Ambient light sensor
43
fault
41—43
MIW-RWTHM-2-ES-000 - 19 / 07 / 2019
TRANSMISOR PARA HABITACIÓN COMBINADO:
TEMPERATURA (T) Y HUMEDAD RELATIVA (HR)
Data type
Description
signed int
Actual temperature level
unsigned int
Output value 1 (T)
Flag indicates that measured Temperature is outside
set alert values. Set to '1' when the measured value
unsigned int
is outside the Temperature alert values defined by
holding registers 13 and 14
Flag indicates that measured temperature is outside
set range limit values. Set to '1' when the measured
unsigned int
temperature is outside limit range values defined by
holding registers 11 and 12
Flag
that
shows
unsigned int
temperature & humidity sensor is lost
signed int
Wall temperature level
Flag indicates that measured Wall Temperature is
outside set alert values. Set to '1' when the measured
unsigned int
value is outside the Wall Temperature alert values
defined by holding registers 17 and 18
Flag indicates that measured Wall Temperature is
outside set range limit values. Set to '1' when the
unsigned int
measured Wall Temperature is outside Wall limit
range values defined by holding registers 15 and 16
Flag
that
shows
unsigned int
temperature sensor is lost wall
unsigned int
Actual relative humidity level
unsigned int
Output value 2 (rH)
Flag indicates that measured Relative humidity is
outside set alert values. Set to '1' when the measured
unsigned int
value is outside the Relative humidity alert values
defined by holding registers 21 and 22
Flag indicates that measured Relative humidity is
outside set range limit values. Set to '1' when the
unsigned int
measured Relative humidity is outside limit range
values defined by holding registers 19 and 20
Flag
that
shows
unsigned int
temperature & humidity sensor is lost
signed int
Calculated dew point
Reserved, return 0.
unsigned int
Measured ambient light intensity
Active or Standby indication according the Active /
Standby light level defined by holding registers 35
unsigned int
and 36. If the measured light level is between the two
levels the indication is 0 (Low light intensity)
Flag that shows if the communication with the
unsigned int
ambient light sensor is lost
Reserved, return 0.
Data
-300—700 500 = 50,0°C
if
the
communication
with
-300—700 500 = 50,0°C
if
the
communication
with
if
the
communication
with
-700—700 200 = 20,0°C
0—32.000 1.000 = 1.000 lux
www.sentera.eu
volver al índice
Values
0—1.000 0 = 0 %
1.000 = 100 %
0—1 0 = Temperature measurement OK
1 = Temperature measurement too low/high
0—1 0 = Temperature range OK
1 = Temperature range too low/high
0—1 0 = No
1 = Yes
0—1 0 = Temperature measurement OK,
1 = Temperature measurement too low/high
0—1 0 = Temperature range OK,
1 = Temperature range too low/high
0—1 0 = No
1 = Yes
0—1.000 1.000 = 100,0 % rH
0—1.000 0 = 0 %
1.000 = 100 %
0 = Relative humidity measurement OK
0—1
1 = Relative humidity measurement too low/
high
0—1 0 = Relative humidity range OK
1 = Relative humidity range too low/high
0—1 0 = No
1 = Yes
0 = Low light intensity
0—2
1 = Active
2 = Standby
0—1 0 = No
1 = Yes
9 - 11