WARNING
Above devices have been developed to safeguard the operator's safety.
6.8
Cleaning
Clean the unit carefully. Remove any dust, foreign substances and dirt possibly deposited during handling.
Use detergents and degreasers.
ATTENTION
Solvents are not allowed.
7
Connecting the unit
ATTENTION
Before connecting the unit make sure that mains voltage and frequency
correspond to the values shown in the data plate. Voltage tolerance: +/- 10% compared
to nominal value.
7.1 Electric connection
Connect the unit after checking the panel components.
ATTENTION
Connection to the electric line shall be effected applying a suitable safety device (a circuit
breaker or a ground fault interrupter) selected by the installer on the basis of the line
involved and of the absorption indicated on the unit plate.
If a cold room includes more units, each unit shall be provided with its own safety device.
Connect the unit paying attention to the colours of the supply cable wires:
We advise to install a microswitch (not supplied) on the cold room door which will
- switch on the light in the cold room, stop the unit and
- override the temperature alarm (for about one hour after door closing)
every time the door is opened.
The necessary cable is available with the unit. Connect it keeping in mind the following:
microswitch closed = door closed.
a) 230V/1/50-60Hz
b) 230V/3/50-60Hz
c) 400/3/50 Hz
3 wires
Blue = Neutral
Yellow/Green = Ground
Brown = Phase
4 wires
Grey = Phase
Yellow/Green = Ground
Brown = Phase
Black = Phase
5 wires
Blue = Neutral
Yellow/Green = Ground
Brown = Phase
Black = Phase
Grey = Phase
21