Descargar Imprimir esta página

Hitachi HC-A16KNX Manual De Instalación Y Funcionamiento página 16

Ocultar thumbs Ver también para HC-A16KNX:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 19
3.3. Configuration Method
Every HC-A16KNX can control up to 16 I.U, considering that in the same H-LINK can be connected up to 160 IU, it must be set
which indoor units are selected for each HC-A16KNX.
Setting concept consist in an "id" table listing up to 16 numbers for the assignation of each OU+IU addresses as shows the following
example.
?
NOTE:
– It can be selected for 1 HC-A16KNX up to 16 I.U from 16 different refrigerant cycles or 16 I.U from the same refrigerant cycle.
Those I.U. must be assigned to a BMS id from 0 to 15, from 16 to 31 must be without any configuration.
&
CAUTION:
– Be sure not to set same Indoor Unit to more than one HC-A16KNX. This error is undetectable and can cause undesired
operations.
– Addresses over id 15 are not used because they cannot be controlled with HC-A16KNX. Using them could create some
problems with the configured units between 0 and 15.
14
PMML0193A rev.2 - 06/2010
Id
Rerigerant cycle address
00
00
01
00
02
00
03
00
04
00
05
00
06
00
07
00
08
00
09
00
10
00
11
00
12
00
13
00
14
00
15
00
Installation
Indoor unit address
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15

Publicidad

loading