Float Control Application Startup
NOTE: Attempting to navigate away from the Auto Mode screen while the pump is in operation will cause a
warning screen to appear. Refer to
NOTE: Float switch(es) on/off status is indicated by the illustration on the screen, but does not accu-
rately portray installation depths.
1.
If not already complete, set up and configure the float(s).
•
Refer to
"Float Control Configuration" on page
2. Return to Auto Mode screen.
3. Use the door mounted dial to adjust the Float Speed.
•
This is the speed the pump will run when the floats call for a run command.
IMPORTANT: Motor rotation will start in the next step.
4. Press ENABLE button.
•
When the floats are activated to call for a run command, the pump will start.
5. Monitor the rotation of the motor fan and shaft coupling.
6. If rotation is incorrect, press FWD/REV and confirm the selection in the pop-up dialog box.
•
The pump will slow to a stop, change direction, and restart automatically.
7.
Adjust speed as required using the door mounted dial.
•
Motor speed will be displayed on the RPM Gauge.
8. Press DISABLE to turn off the pump and deactivate auto mode.
"Auto Mode" on page
24.
8
4
17.
6
7
OPERATION
Auto Mode
25