Fault
The heater produces
white smoke.
The heater uses too
much fuel.
Heater cannot be
switched off.
The cooling thermo-
stat does not switch
on/off.
The automatic cooling
does not work / does
not stop.
Record the maintenance details in table A in
the appendix at the back of this book.
7
SPARE PARTS
For operation we advise you to have spare
parts in store. See table B in the appendix.
8
TECHNICAL INFORMATION
For the technical specifications, see table
C in the appendix at the back of this
book.
ITA 35 R
ITA/ITAS
Cause
20
The fuel system has air. See fault 6.
21
The nozzle is too big or
the wrong type is used.
22
The magnetic valve
does not close.
23
The automatic cooling
does not work.
24
The after cooling ther-
mostat does not switch
on/off.
41.350.095 rev 01 - 2021
40.020.005 - rev. 07 - 2011
Solution
Replace the nozzle with the
correct one.
Check the fuel pipes.
See faults 10 and 18.
Remove the fuel line from
the filter to extinguish the
flame.
Clean or replace the mag-
netic valve.
Remove the fuel line from
the filter: the flame will extin-
guish.
Cooling is required for 4
minutes. Remove the plug
from the socket.
English
Action
User
User
User
User
Dealer
Dealer
Dealer
21
21