DK 5000 - 10000 ECO
12
Troubleshooting
Observe the safety instructions!
Problem
The compressor does not
operate even though the
operating indicator is lit.
The fan does not operate
even though the operat-
ing indicator is lit.
Water in the system
High pressure decrease
14
Cause
Overpressure switch
for
the
refrigerant
triggered.
Ambient temperature too
high.
Condenser
clogged
dust.
Electrical fault.
Fuse has triggered.
Fan must operate when
the
refrigerant
pressure
reaches the upper switch-
ing threshold.
Condensate discharge
blocked/faulty.
Bypass line open.
Excessive humidity.
Condenser
clogged
dust.
Refrigerant system
does not work.
Input air filter
clogged.
Lines frozen.
Remedy
Press the green button to reset the
has
switch.
Decrease the ambient temperature by
ventilating the room where the dryer
is operating.
Operate the dryer below the maxi-
mum values.
with
Clean the condenser.
Check the components / wiring.
Replace the fuse. If the problem per-
sists, call our service hotline.
Make sure that the air flow is ade-
quate. The fan must rotate freely.
Unblock/repair the condensate dis-
charge, check the drying perfor-
mance.
Check the stop cock.
Check the water separator.
with
Clean the condenser.
Make sure that the compressor and
fan are operating. If not, call our ser-
vice hotline.
Replace the filter element.
Room temperature must be higher
than 5°C.
Have a service technician check the
dryer settings.