Descargar Imprimir esta página

Panasonic PAW-SERVER-PKEA-1 V5.2 Instrucciones De Instalación página 7

Interfaz control de backup servidores, para interfaz control de backup

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Here are the functions available:
INPUT (NO Voltage):
(I1 – I1) ->
(I2 – I2) ->
OUTPUT (Max. 48 Volt - 3 Ampere):
(O1 – O1) ->
(O2 – O2) ->
(O3 – O3) ->
(O4 – O4) ->
Connection example:
CN-RMT
A1 A2 A3 A4 B1 B2 B3 B4
I1 I1 I2 I2 O1 O1 O2 O2 O3 O3 O4 O4
Dip-Switch n. 3 is ON: Short Circuit -> Set Unit "A" ON.
Dip-Switch n. 3 is ON: Open Circuit -> Set Unit "A" OFF.
Dip-Switch n. 3 is OFF: Change from Short to Open Circuit -> System OFF.
Dip-Switch n. 3 is OFF: Change from Open to Short Circuit -> System ON.
Same functions as above described for Unit "B"
Note: For Restart function dry contact inputs I1 and I2 need a jumper (one for
each input terminal)
Always available.
Short Circuit -> ON state of unit "A".
Open Circuit -> OFF state of unit "A".
Always available.
Short Circuit -> ON state of unit "B".
Open Circuit -> OFF state of unit "B".
Always available.
Short Circuit -> NO Alarm unit "A".
Open Circuit -> ALARM unit "A".
Always available.
Short Circuit -> NO Alarm unit "B".
Open Circuit -> ALARM unit "B".
ALARM
Unit "B"
Deatail 2
NO
Set OFF/ON unit "B"
Set OFF/ON unit "A"
ALARM
Unit "A"
NC
NO
NO
NC
7
Dry Contacts
24 Vac
ON State
ON State
Unit "A"
Unit "B"
NC
NO
NC
EN

Publicidad

loading