4. INSTALLATION
This product should be installed by a qualified electrician.
During installation ensure that the remote connector with wire bridge is removed (or swtich off the remote on/off switch if
installed) to be sure that the inverter cannot be switched on unexpectedly.
4.1 Location
The product must be installed in a dry and well-ventilated area, as close as possible to the batteries. There should be a clear space of at
least 10cm around the appliance for cooling.
Excessively high ambient temperature will result in the following:
Reduced service life.
Reduced charging current.
Reduced peak capacity, or shutdown of the inverter.
Never mount the appliance directly above the batteries.
The product is suitable for wall mounting. For mounting see appendix A.
The appliance can be mounted horizontally as well as vertically; vertical mounting is preferable. The vertical position offers optimum
cooling.
The interior of the product must remain accessible after installation.
Try and keep the distance between the product and the battery to a minimum in order to minimize cable voltage losses.
For safety purposes, this product should be installed in a heat-
resistant environment if it is used with equipment where a
substantial amount of power is to be converted. You should
prevent the presence of e.g. chemicals, synthetic components,
curtains or other textiles, etc., in the immediate vicinity.
4.2 Connection of Battery cables
In order to fully utilize the full capacity of the product, batteries with sufficient capacity and battery cables with sufficient cross section
should be used. See table.
12/1600
Recommended fuse
250A
Recommended cross
section (mm
)
2
0 – 5 m
5 -10 m
Not recommended
12/3000
Recommended fuse
400A
Recommended cross
section (mm
2
)
0 – 5 m
2x 95*
5 -10 m
Not recommended
*One cable must be sized to carry the rated fuse current without overheating.
Do not locate battery cables in a closed conduit.
Please follow local installation rules.
12/1600
Recommended
300 - 800
battery capacity (Ah)
12/3000
Recommended
400 - 1200
battery capacity (Ah)
24/1600
125A
70
35
70
24/3000
250A
1x 50
2x 50
24/1600
150 - 400
24/3000
200 - 700
48/1600
12/2000
60A
300A
16
70
25
Not recommended
48/3000
24/5000
125
400A
1x 35
2x 95*
2x 35
2x 95
48/1600
12/2000
75 - 200
350 - 1000
48/3000
24/5000
100 - 400
300 - 1500
24/2000
48/2000
150A
80A
50
25
95
50
48/5000
200A
1x 70
2x 70
24/2000
48/2000
200 - 500
100 - 250
48/5000
150 - 700
5