Descargar Imprimir esta página

Sam FL-12 Manual De Instrucciones página 21

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 46
DC Volts
Range
660mV
6.6V
66V
660V
1000V
Overload protection: 1000V DC or 750V AC rms
AC Volts (True RMS)
Range
660mV
6.6V
66V
660V
750V
Crest Factor:  3
Peak Hold: ±(3.0% rdg + 200 dgts) on 66V to 750V ranges
AC coupled true rms specified from 5% to 100% of range
FREQUENCY Ranges: 50Hz ~ 1kHz.
Accuracy: ± (0.1% rdg + 5 dgts)
Minimum Input voltage Range: >500dgts.
The readings of frequency measurements will show on the sub-
display.
Overload protection: 1000V DC or 750V AC rms
AC current (True RMS)
Range
660A
1500A
Crest Factor:  3
Peak Hold: ±(3.0% rdg + 200 dgts)
AC coupled true rms specified from 5% to 100% of range
FREQUENCY Ranges: 50Hz ~ 1kHz.
Accuracy: ± (0.1% rdg + 5 dgts)
Minimum Input current Range: >500dgts.
The readings of frequency measurements will show on the sub-display.
Overload protection: 1500A AC.
DC current
Range
660A
2000A
Overload protection: 2000A DC for 60 seconds maximum.
Version : 2023/06/26
Resolution
Accuracy
0.1mV
± (0.5% rdg + 2d)
1mV
± (0.5% rdg + 2d)
10mV
± (0.5% rdg + 2d)
100mV
± (0.5% rdg + 2d)
1V
± (0.5% rdg + 2d)
Accuracy (50~500Hz)
Resolution
0.1mV
± (1.5% rdg + 8d) 50~100Hz
1mV
± (1.5% rdg + 8d) 50~500Hz
10mV
± (1.5% rdg + 8d) 50~500Hz
100mV
± (1.5% rdg + 8d) 50~500Hz
1V
± (1.5% rdg + 8d) 50~500Hz
Resolution
Accuracy (50 ~ 400Hz)
0.1A
0~660A±(2.0% rdg+10d)50~60Hz
0~660A±(3.0% rdg+10d)61~400Hz
1A
660~1000A±(2.5% rdg+10d)50~60Hz
660~1000A±(3.5% rdg+10d)61~400Hz
1000~1500A±(5.0% rdg+10d)50~400Hz
Resolution
0.1A
0~660A±(2.0% rdg+5d)
1A
660~1000A±(3.0% rdg+5d)
1000~2000A±(5.0% rdg+5d)
Input Impedance
>100MΩ
10MΩ
9.1MΩ
9.1MΩ
9.1M Ω
Input Impedance
> 100MΩ
10MΩ
9.1MΩ
9.1MΩ
9.1MΩ
Accuracy
21 / 67