Descargar Imprimir esta página

Mitsubishi Electric TRANE CITY MULTI TPKFYP LM140 Serie Manual De Instalación página 10

Ocultar thumbs Ver también para TRANE CITY MULTI TPKFYP LM140 Serie:

Publicidad

Idiomas disponibles

Idiomas disponibles

6. Electrical work
A
J,K,L
M
I
S
en
P
L
9
B
C
F,G,H
E
D
F
N
H
O
G
J
K
L
R
Q
T
6.1. Electric wiring
[Fig. 6-1]
Connection can be made without removing the front panel.
1. Open the front grille, remove the screw (2 pieces), and remove the electrical
parts cover.
* Electrical work can be conducted more effectively with the panel removed.
When attaching the panel, check that the hooks T at three locations on the air
outlet side are connected securely.
2. Securely connect each wire to the terminal block.
* In consideration of servicing, provide extra length for each of the wires.
* Take care when using strand wires, because beards may cause the wiring to
short out.
3. Install the parts that were removed back to their original condition.
4. When going through the right side of the indoor unit, cut out the removable
section of the Corner box E.
Front grille
A
Fixing screw
B
Electrical box cover
C
Fixing screw
D
Corner box
E
Conduit plate
F
Conduit cover
G
Fixing screw
H
Fixing screw
I
Remote control cable
J
Transmission cable
K
Power supply cable
L
Lock nut
M
Conduit joint
N
Conduit pipe
O
Ground wire connection portion: Connect the ground wire in the direction illustrated in the
P
Q
MA remote control terminal block: (1, 2) do not have polarity
Transmission terminal block: (M1, M2, S) do not have polarity
R
Power supply terminal block (L1 , L2)
S
Hook
T
Caution:
Wiring for remote controller cable shall be apart (5 cm, 1-31/32 inch or more)
from power source wiring so that it is not influenced by electric noise from
power source wiring.
When going through the right side
Fig. 6-1
diagram.
E

Publicidad

loading