Electrical Specifications
Item
NCV Range
NCV Signal
Indications
Battery
Power Consumption Max 60mA @ 9V
Battery Life
Buzzer Volume
Item
Operating Voltage
Operating
Frequency
GFCI Trigger
Current
Power Consumption 120V AC Max 1.5W
GFCI Button
Wiring Condition
Indications
Overload Protection 240 RMS
Range/Specs
80-300VAC, 60Hz,
1" of the energized
conductor
The red LED flashes and the buzzer beeps intermittently (beeps
frequency according to the sense voltage, 35V: 2Hz flash/beep;
60V: 4Hz flash, 4Hz beep; 85V: 10Hz flash, 10Hz beep)
9V
2.5 hrs.
Approximate 60dB @ 10cm
Range/Specs
100-120V AC
60Hz
6.0mA-9.0mA
Press the GFCI button to start the GFCI test; release the GFCI
button to stop the GFCI test; (Note: Pressing time is less than 6
seconds, it should trigger the switch to trip. If the pressing time
is greater than 6 seconds, and the breaker/outlet does not trip,
the breaker/outlet may be broken or the GFCI function is not
working.) Note: A valid ground conductor must be present for
this test method to work.
100 ~ 120V AC
Remarks
The receiver tip must be within 2cm
of the energized conductor in order to
sense the presence of AC voltage.
Power off: 2uA
Remarks
Use for 3 wire North American outlets only
(100-120V AC).
GFCI test voltage range AC: 102V
(6mA) - 132V(9mA), only GFCI trip is
triggered(under normal voltage range and
correct wiring, pressing the GFCI button
will trigger GFCI function)
15