Digital input*. Allows you to activate or deactivate this function and change:
Settings. Allows you to set the input as normally open or normally closed.
a.
Activation by state: the state is persistent, if the input is activated the machine will be
forced off until it changes state.
b.
Activation by edge: the status is punctual, only the on/off is sent when the opening
or closing condition is met for the first time.
EN
Time to turn off (minutes). Displays a drop-down for selecting the time (in minutes)
that you want to elapse before turning off the equipment after receiving the signal. If
disabled, the equipment will automatically turn off after receiving the signal.
Time to turn on (minutes). Allows you to select the time (in minutes) that must elapse
with the signal deactivated before the equipment turns on again. This setting only turns
on the equipment if it has previously been turned off. If it is disabled, the equipment
must be switched on again manually.
* In air to water units with 2 water circuits, the digital input only affects to circuit 1.