4.2. Electrical connections to terminal blocks
4.2.1.
Power supply terminals
The power supply terminal block is a 3-pole screw terminal block to be connected to the
corresponding location on the AVS75.
Each AVS75 used in the installation must have a 230VAC 50Hz power supply
Borniers bus de communication :
1
case: Just one module
st
2
case: Several modules
nd
module 3
(if présent)
X30
Issue: 03 / 2023
It is imperative to properly connect this accessory to
the earth and to comply with the national standards in
force in the country concerning low voltage electrical
installations.
ATTENTION :
Provide a bipolar break upstream (distance between
contacts: 3.5 mm minimum).
It is strongly recommended to equip the electrical
installation with a 30 mA differential protection and a
10A circuit breaker/fuse
module 2
X50
BSB buses supplied
with the modules
External AVS 75 expansion module - Accessory
X30
module 1
X50
X30
Alimentation issue de
l'armoire électrique
AVS75 communication
wiring to Navistem
AVS75
X30
communication
wiring to
Navistem
Page 9 / 18