UNITS INSTALLATION
RPI-(2.0-3.0)FSN5E
RPI-(4.0-6.0)FSN5E
Mounting the suspension bolts
-
Using the dimension shown above select the final
location and installation direction of the Indoor Unit
paying careful attention to the space for the piping, wiring
and maintenance.
-
Install the sling bolts, M10 or greater are also
recommended, and suspend the indoor unit using the
following steps:
1 Hook suspension bracket to the nut and washer of each sling
bolt, as shown, starting from one side.
2 After check the nut and washer are correctly fixes by the
retainers of the suspension bracket, hook the suspension
bracket of the other side to nut and washer.
8
PMML0385 rev.0 - 07/2017
Nut
Washer
Suspension
bracket
Left side
Drain pan level
FRONT VIEW
Condensate drain connection
Make sure that the foundation is flat, taking into account
-
the maximum foundation gradient.
-
The unit should be installed so that one side of the unit
is slightly (approximately 5 mm) lower than the other
side, in order to avoid the incorrect position of the drain
discharge.
Tighten the nuts of the suspension bolts with the suspension
brackets after adjustment is completed. Special plastic paint
must be applied to the bolts and nuts in order to prevent them
from loosening.
?
N O T E
Keep the unit as well as relevant equipment covered with the vinyl cover
during installation work.
Suspension
bolt
Washer
Nut
Inlet air
Right side