Output 1 Line
Output 1 Neutral
Output 2 Line
Output Line
Output Neutral
NOTE 1: Make sure that the wires are connected tightly with the terminals.
NOTE 2: There are two kinds of outputs: output terminal/outlets and programmable terminal. Please
connect non-critical devices to the programmable terminal and critical devices to the output terminal/outlets.
During power failure, you may extend the backup time to critical devices by setting shorter backup time for
non-critical devices.
NOTE 3: The internal output breaker is used to cut off the output, but we suggest you to install an external
output breaker between the output terminal and the load. This breaker should be installed in an easy
access area which will allow you to cut off the output immediately in an emergency. And the breaker should
be equipped with leakage current protection if necessary.
6)
Put the terminal block cover back to the rear panel of the UPS.
Warning: (Only for standard model)
● Make sure the UPS is not turned on before installation. The UPS should not be turned on during wiring
connection.
● Do not try to modify the standard model to the long-run model. Particularly, do not try to connect the
standard internal battery to the external battery. The battery type and voltage may be different. If you
connect them together, it maybe causes the hazard of electric shock or fire!
Warning: (Only for long-run model)
● Make sure a DC breaker or other protection device between UPS and external battery pack is installed.
If not, please install it carefully. Switch off the battery breaker before installation.
Terminal Block wiring diagram of 6K(L)/10K(L)
Terminal Block wiring diagram for 6KR(L)/10KR(L)
Input Neutral
Input Line
Ground
7
Input Neutral
Input Line
Output 2 Neutral