Descargar Imprimir esta página

TDK-Lambda DPP120 1 Serie Manual De Instalación página 7

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 5
DPP120-XX-1 Installation Manual
Special Safety Instructions
Standard Specific Safety Instructions:
Whilst all individual outputs are classed as SELV outputs in accordance with the standard IEC/EN/UL/CSA60950-1
(<60Vdc or 42.4V peak), seriesed combinations of these outputs may exceed these
values and become hazardous output voltages.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment
may be impaired.
Environmental Specifications:
Description
Operation
Storage
Use
Indoor
-
Temperature
-25°C - +71°C (derating at 2.5%/°C from 61°C)
-25°C - +85°C
Humidity
20 - 95% RH, non-condensing
20 - 95% RH, non-
condensing
Altitude
2000M
4850m (IEC60068-2-13)
Orientation
See Fig 1
ALL
Material Group
IIIb
Pollution Degree
2
Class
I
Level of Insulation:
Dielectric Strength testing is carried out as follows:
Primary mains circuit to earth: - 1500KVAC, 2121VDC
Primary mains circuits to secondary: 3kVAC, 4142VDC*
*This test is not possible with Y capacitors fitted to the unit as damage to these
capacitors will occur. It is also necessary to short circuit the output together and to earth.
Safety Approvals:
UL508
UL/cUL60950-1 (2
Edition)
nd
IEC / EN60950-1(2
Edition)
nd
CE marking when applied to any DPP120-xx-1 product indicates compliance with the Low Voltage Directive
(2006/95/EC) in that it complies with EN60950-1 (2
Edition).
nd
Fusing: Internal fuses (F1): Single fuse in the L line, T3.15AH, 250V, 5x20mm.
Symbols:
N
L
AC
EARTH
N – Neutral
L – Live
If the earth terminal of the DPP120-XX-1 PSU is connected to the main incoming earth conductor of the end
equipment, the installer must cover the earth symbol with a label bearing the earth symbol of IEC60417-5019.
Page 7 of 10
October 2023
UM000013A01

Publicidad

loading