OPERATION
CAUTION: DO NOT THROW ITEMS INTO THE STORAGE AREA. FAILURE TO HEED THESE
RECOMMENDATIONS COULD RESULT IN DAMAGE TO THE INTERIOR OF THE
CABINET.
REFRIGERATION CYCLE
REFRIGERATORS: During the refrigeration cycle, the evaporator fans wilt run
continuously even when one or more doors are open. The door switch will activate
the lights when opened. Every 6 hours, the unit will turn off to let the evaporator
coil clear up the ice. The controller now displays the defrost symbol. When the
coil temperature reaches 41°F or after 20 minutes of defrost, the unit will turn on
again. The factory setting of the temperature range is 34 to 38°F.
FREEZERS: During the refrigeration cycle, the controller supplies power to the
condensing unit and evaporator fan motors. The evaporator fan will run at any time
when the evaporator coil temperature is below 54°F and it will cycle off during
the defrost period. Every 6 hours, the unit will turn off and the defrost heater will
work to clear up the ice. The controller now displays the defrost symbol. When the
coil temperature reaches 45°F or after 20 minutes of defrost, the unit will turn on
again. Anti-Condensation heaters on the door frames work in conjunction with
the compressor. The factory setting of the temperature range is -7 to -3°F
CONTROL PANEL SOLID-STATE THERMOSTAT
FRONT PANEL COMMANDS
SET
SET: To display target set point; in programming mode it selects a
parameter or confirms an operation.
DEF: To start a manual defrost
UP: To view the last alarm occurrence; in programming mode it browses
the parameter codes or increases the display value
DOWN: To view the last alarm occurrence; in programming mode it
browses the parameter codes or decreases the display value
Key Combination:
To lock & unlock the keyboard
To enter in programming mode
To return to the room temperature display
1.1 Function of LEDS
1.1 Function of LEDS
LED
MODE
On
Compressor enabled
Flashing Programming phase (flashing with
Anti-short cycle delay enabled
On
Defrost enabled
Flashing Programming phase (flashing with
Dripping in progress
On
Fans enabled
Flashing Fans delay after defrost in progress
On
A temperature alarm happened
2. MAIN FUNCTIONS
3
UPRIGHT CHILLER & FREEZER
2. MAIN FUNCTIONS
FUNCTION
)
)
MAIN FUNCTIONS
1. How to See the Setpoint
1. Push and immediately release the SET key: the display will show the set
point value.
2. Push and immediately release the SET key or wait for 5 seconds to display
the sensor value again.
2. How to Change the Setpoint
1. Hold the SET key for more than 2 seconds to change the set point value.
2. The value of the set point will be displayed and the
3. To change the set value, push the
4. To set new point value, push the SET key again or wait 10 seconds.
3. How to Start a Manual Defrost
1. Hold the
key for more than 2 seconds and a manual defrost will start.
4. How to Lock the Keyboard
1. Hold the
and
keys for more than 3 seconds.
2. The "POF" message will be displayed and the keyboard will be locked. At
this point, it will be possible only to see the set point or the MAX or MIN
temperature stored.
3. If a key is pressed for more than 3 seconds, the "POF" message will be
displayed.
5. How to Unlock the Keyboard
1. Hold the
and
keys together for more than 3 seconds, until the "POF"
message is displayed.
ALARM SIGNALS
How to See the Alarm and Reset the Recorded Alarm
1. Push the
or
key to display the alarm signals.
2. When the signal is displayed, hold the SET key until the "rst" message is
displayed. Push the SET key again. The "rst" message starts blinking and the
normal temperature will be displayed again.
MESSAGE
CAUSE
"P1"
Room probe failure
"P2"
Evaporator probe failure
"HA"
Maximum temperature alarm
"LA"
Minimum temperature alarm
"dA"
Door open
"EA"
External alarm
"CA"
Serious external alarm (i1F=bAL)
Service and Installation Manual
"CA"
Pressure switch alarm (i1F=PAL)
Service and Installation Manual
LED starts blinking.
or
key within 10 seconds.
OUTPUTS
Compressor output according
to par. "Con" and "COF"
Defrost end is timed
Outputs unchanged
Outputs unchanged
Compressor and fans restarts
Output unchanged
All outputs OFF
All outputs OFF