terminal. Make the electrical connections observing the
polarity. Connect the positive input loop line to "Is+"
terminal (in the middle) in case the built-in isolator module
should be used. Then mount back the 5-position plug to
the PCB terminal.
45RFU100
Min. 2m
45PAM100
Description of loop wiring:
"Loop IN -" Connect negative input wire of the loop line.
"Loop IN +" Connect positive input wire of the loop line.
"Loop IN Iz+" Connect to "Iz+" terminal in case the
built-in isolator module is used.
"Loop OUT -" Connect negative output wire of the loop
line.
"Loop OUT +" Connect positive output wire of the loop
Connection with using the built-in isolator
L- L+ lz+ L- L+
L- L+ lz+ L- L+
Loop IN
Loop IN
Connection without using the built-in isolator
L- L+ lz+ L- L+
L- L+ lz+ L- L+
Loop IN
Loop IN
line.
8. Front Panel
At the front panel of 45TRA100,
are located LCD text display and
operation buttons.
1
1. Antenna (mounted to the
2
antenna connector on the PCB).
2. LCD text display, dot matrix
3
16x2.
3. LED indication for the module
4
status:
Symbol
LED
State
Min. 2m
45SCI100
45RML100
Min. 2m
Loop OUT
Loop OUT
Loop OUT
Loop OUT
Description
Blinking at 10sec intervals
red
Lighting on
green
Lighting on
4. Operation buttons:
Button
Function
Description
Enter in selected programming menu.
ENTER
Confirmation of operation or introduced settings.
Exit from programming menu. Reject the
CANCEL
operation or introduced settings.
Button for scrolling up/down the programming
UP/DOWN
menus or available settings.
9. Addressing of 45TRA100 to LogiFire
41CPE118 Fire Alarm Panel
Every 45TRA100 module has a factory ID number
for addressing in 41CPE118 fire alarm control panel.
After the connection to the loop line and power-up
of the module, the 41CPE118 panel will recognize it
automatically with system name "45TRA100".
Attention: The 45TRA100 module takes one address
number as loop connected device. The following 32
address numbers will be kept reserved for all Comelit
series wireless fire alarm devices enrolled to that
specific module.
It is recommended to plan the system configuration
in advance as:
- In new installation, add the expander module as first
device to the loop. Thus, you will reserve the next 32
addresses ensuring the future expanding with wireless
devices avoiding doubling of addresses and other system
conflicts.
- In present installation, research the free addresses
in the loop. You need of 33 consecutive free address
numbers in the loop line to ensure the normal addressing
of the wireless devices.
Note: Never add the 45TRA100 wireless expander
module between other present already taken
addresses in the configuration. That will result
in system conflicts and doubling of addresses!
The enrolled devices will be set automatically in
consecutive addresses following the order and
numbering of enrollment to the module.
All added devices to 41CPE118 configuration must be
saved with pressing "APPLY" button on the upper left
corner of the screen. The ID number, software revision
and the available setting for the device are available after
pressing the MORE button.
Attention: If the wireless expander module is deleted
from 41CPE118 system configuration (REMOVE
button), the wireless devices saved at the next
addresses will be deleted too from the 41CPE118
system configuration.
10. Initial Power-up of 45TRA100
1. Research the fire installation and choose loop line
providing at least 33 free consecutive address numbers.
2. Switch off the main and back-up power supply of
41CPE118 fire alarm panel.
3. Open the enclosure box of the expander module and
mount it on the place of installation – see item 4.
4. Connect 45TRA100 module to the loop line observing
Communication with the
enrolled devices.
Selected device from the
panel (button TURN ON).
Programming mode entry.
9