Input configuration
Allows you to configure the behaviour of the digital inputs.
Send "I(n), <NC/NO>, <persistence time>, <message>"
Number of the input to be configured.
<n>
Defines the input polarity:
<NC/NO>
Time in seconds that the input must remain active to send an alert.
<persist. t.>
Message that will be received if the alarm for the configured input is activated.
<message>
Example: To configure input 2 as a normally open contact, with a persistence time of 15 seconds and a
customised alert message, send:
After a few seconds, the alarm responds with the message*:
I2 OK
Customisation of power failure message
Change the alert message for power failure or restoration of power.
Send "BATMSG,<message OFF>,<message ON>
message
Message in the event of power failure
<
OFF>
message
Message in the event of power being restored
<
ON>
Example: Send:
After a few seconds, the alarm responds with the message*:
BATMSG OK
Customisation of the reset message
Change the alert message for the alarm reset. This message is sent only to the first number on the
telephone list.
Example: Send "RESETMSG, <message>
After a few seconds, the alarm responds with the message*:
RESETMSG OK
*If you receive an error message, refer to page 25.
NO: Normally open, the alarm is activated on closing.
NC: Normally closed, the alarm is activated on opening.
I2,NO,15,High temperature
in frozen food cold room
BATMSG,Power failure,
Power has been restored
RESETMSG, The alarm has been reset