GB
start-up
Warning
To ensure the safety and correct operation
of the module, the latter must be started-
up by a legally qualifi ed and authorised
technician.
Ignition procedure
- Power the module.
- Remove the cover of the control unit con-
nection shoe (see electrical diagram).
- Insert the system interface into the con-
nection shoe by pushing it gently down-
wards; after a brief initialisation, the sys-
tem interface will be connected.
- The display will visualise Error 214 "hy-
draulics diagram not defi ned".
- Simultaneously press the back "
"OK" buttons until "Enter code" appears
on the display.
- Turn the knob to enter the technical code
(234) then press OK; the display will visu-
alise TECHNICAL AREA:
- Language, date and time
- Guided confi guration
- Maintenance
- Errors
- Complete menu
In order to facilitate the solar parameter
setting operations, without accessing the
complete Menu, it is possible to perform
the confi guration through the rapid access
menu:
- Guided confi guration.
Turn the knob and select:
- GUIDED CONFIGURATION
Press the OK button.
The display will visualise the list of devices
present in the system:
- System interface (local)
- Solar control
- ...
- Confi rm components
40
The confi gurable devices are marked by the
"
" symbol.
To select the hydraulics diagram and type
of pump unit, turn the knob and select:
- Solar control
Press the OK button.
Turn the knob and select the type of indi-
rect cylinder used, among the following:
-
-
Press the OK button.
- Type of pump unit
Turn the knob and select:
- Digital
The display will visualise the type of hy-
draulics diagram used.
" and
Press OK to confi rm the choice, or press
the back button "
ous visualisation.
Turn the knob and select:
- Confi rm components
Press OK if the list of installed components
is complete, otherwise verify the connec-
tions of the devices not appearing in the list.
To confi gure the peripherals, turn the knob
and select:
- Solar control
Press the OK button.
Turn the knob and select among the follow-
ing:
- Parameters
- Test mode
- Guided procedures
Turn the knob and select:
- PARAMETERS
(allows for visualising and setting the es-
sential parameters for the system's correct
operation)
Press the OK button.
- Solar confi guration
Press the OK button.
Turn the knob and select:
- 3 2 0 Anti-Legionnaire's disease func-
tion
Turn the knob to set the anti-Legionnaire's
-
" to return to the previ-