The HTG411L is a multi-energy data logger and server
delivered with a 4GB micro SD card. It is intended to
configure systems and products, collect, store and time
stamp information for connected products. It processes
this information and monitors the quality of the electrical
distribution and makes it available to the user through an
embedded webserver. This product is accessible from
the Internet network.
This device is to be installed only by a
professional electrician fitter according
to local applicable installation standards.
Do not install this module outside the
building.
Power supply over Ethernet (PoE) prohi-
bited.
In «Setup ON» mode, the HTG411L acti-
vates its DHCP server on «Setup - Ether-
net 1» port.
Installation
The HTG411L must be fitted on a DIN rail.
Implementation
1. Connect the inputs / outputs on the HTG411L termi-
nal block.
2. Connect the Modbus and Ethernet networks as
appropriate.
3. Enable 120 Ω termination resistor (selector (2) to
set to «ON») if the product is fitted at the end of the
Modbus network.
4. Check that the selector «Setup» (1) is in «OFF»
position.
5. Connect the 24 V s power supply (SELV).
Front face and connections
Digital
Output relay
24 V s SELV
24 V s
0,6 A
HTG411L
Setup
Setup (1)
ON
Selector
OFF
Led
Modbus
RS485
Termination
resistor
120
Modbus RS485 (2)
LED information
LED
Colour
Power
Green
Green
or orange
Red
Red or orange Fixed
Modbus
Green
RS485 /
Ethernet 1 /
Ethernet 2
Red
02
First configuration
1. Start the software update:
a) download the latest software version from
https://hgr.io/r/htg411l
b) unzip the downloaded file
c) read the file «readme.txt»
2. Connect the computer to the RJ45
«Setup - Ehernet 1» connector of HTG411L using
the Ethernet cable.
3. Turn switch «Setup» (1) in «ON» position.
4. Perform a reset by switching the power
supply off and again on.
5. Activate the Web browser on the computer.
6. Enter: url : https://192.168.0.1
7. Setting the HTG411L, refer to the user guide, down-
loadable from https://hgr.io/r/htg411l website or
with the Datamatrix scanning.
The energy server has two operating modes:
- Stand-alone mode : The server is still the master
component in the installation and obtains measure-
ments from connected meters.
- Supervised mode: The server is used as a gateway to
send data to the Energy Management System stream.
Several functions in the menus are inaccessible in this
mode (see user manual).
Switch to supervised mode
1. Go to the Preferences menu.
2. Select the System tab.
3. In the Supervised mode section, check yes to
enable the mode.
4. Click on Save.
When the energy server is rebooted, it restarts in
supervised mode.
Output
Output
Input
PT100
Modbus
6 0
6 0
State
Status
Fixed
Functional product.
Blinking
Product initialisation.
Blinking
Product enters in power reserve.
Software startup problem.
Off
Product not powered.
Fixed / blinking
Connected and functional network.
Off
No communication network detected.
Fixed / blinking
Communication fault.
login : admin
password : admin
Analog
PT100 input
LED
Ethernet 1
Ethernet 2
Power ON
USB 2.0
Micro SD memory card slot
1
2
RJ45 port Modbus RS485
pin4: D1 or B/B' or "+" / green wire
pin5: D0 or A/A' or "-" / yellow wire
pin8: Common or C/C' or 0VL / brown wire
3
Not used
I
mportant: The RS485 Modbus circuits must be connected only to external
RS485 Modbus circuits that are Safety Extra-Low Voltage (SELV).
Solution
/
Wait for initialisation.
If the indication remains, refer to manual.
Wait during the shutdown progress.
Perform a reset by switching the power supply off.
Wait for LED to switch off before switching the power supply on.
If the indication remains, refer to manual.
Check the power supply.
/
Check the connection.
Check the configuration of links.
Technical characteristics
External safety extra low voltage power supply
..................................... 24 V s (SELV) +/- 10 %
Typical consumption ......................................7 VA
Ethernet network com munication .........................
...........Ethernet - TCP / IP - RJ45 / 100 base - T /
......................................................... IEEE 802.3
Modbus network com munication ..........................
........................................ RS485 Modbus RJ45
Operating temperature .................. -25° to +55°C*
Storage temperature ...................... -55° to +85°C
Humidity storage ............... 95 % max HR at 55°C
PT100 input ...................................... 2-wire probe
....................................... EN 60751 compliance
Binary digital output ..................... 5 to 30 V s / v
.......................................................10 mA to 3 A
......................................... resistive dry contact
Number of relay cycles ..............................100000
Power supply, digital output connection ...............
.................................................... 0.75 - 2.5 mm²
Analog input connection .................. 0.2 - 1.5 mm²
Degree of protection ......................................IP 20
Weight .......................................................... 290 g
Maximum operating altitude ..................... 2 000 m
Micro SD card ......................................... Class 10
USB port 1 (front face)...........................................
.................. USB 2.0 Type A standard connector
USB port 2 (under the product) .............................
.................. USB 2.0 Type A standard connector
*: The use of product at the maximal temperature can reduce its life
expectancy.
Prerequisite for installation:
- Equipment:
- A computer with internet browser
(Chrome recommended),
- an RJ45 Ethernet cable.
In case of an extended Ethernet network:
- an Ethernet network socket,
- product name on the network,
- a static or dynamic IP address,
- the network mask.
Setup
1
1
Modbus RS485
8
1
2
3
4
5
USB 2.0
4
5
RJ45 Setup port - Ethernet 1
6
RJ45 port - Ethernet 2
2
6

Publicidad

loading