Descargar Imprimir esta página

DINUY TM KNT 001 Instrucciones De Uso página 2

Termostato táctil capacitivo knx

Publicidad

Idiomas disponibles

Idiomas disponibles

EN
INSTRUCTIONS MANUAL
Ref. TM KNT 001 / TM KNT 002
KNX CAPACITIVE TOUCH THERMOSTAT
TM KNT 001
TECHNICAL SPECIFICATIONS
Supply Voltage
Bus Current
Type of connection
Programming by
KNX Topology
Commissioning
Compatible
Temperature Probe
Temperature
Probe range
Maximum length
of the cable
Temperature
Relative Humidity
Display
Working Temperature
Storage Temperature
Degree of protection
Directives
Standards
DIMENSIONS
CHARACTERISTICS
● KNX Capacitive Touch Thermostat for room temperature control.
● Two different models are available:
· TM KNT 001: with button for adjusting the fan speed of the
Fan-coil
· TM KNT 002: with button to adjust the HVAC operating mode.
L
I
J
K
● It incorporates a Display (D) that shows both the Setpoint or Ambient
Temperature and the Relative Humidity of the environment.
● It has 4 buttons with preset functionality:
· Decrease Set-point Temperature (I).
· Increase Set-point Temperature (F).
· Switch On/Off Thermostat (J).
· Fan-Coil Speed or HVAC Mode (G).
● In addition, there are 2 free buttons (H and K), which can be
configured as a Switch, Dimmer, Control of Blinds / Shutters, Scenes,
etc..
● Integrated Temperature Sensor, Brightness Sensor (L) and Relative
Humidity.
● Fancoil Speed or HVAC Mode (E) LED.
● Its main functionality is complemented with 4 Binary / Analog Inputs
(C), which can be connected to a Door / Window Contact or a DINUY
Temperature Probe.
● Allows enabling and configuring one Heating and / or Cooling
Thermostat. Press or status indicator LEDs with ETS configurable
luminosity and RGB color on the 2 freely configurable keys (H and K)
● No need external power, only the KNX Bus.
● KNX Bus Coupling Unit (BCU) integrated.
● Designed for flush mounting into universal mechanism boxes.
● Commissioning by ETS5 or later versions.
DESCRIPTION
B
The Thermostat consists of different elements (Fig. 1):
· Programming LED and button (A).
· KNX bus connector (B).
· Inputs for Temperature Probe or Door Contact (C).
MOUNTING AND INSTALLATION
Installation and assembly of electrical equipment
must be carried out only by a skilled person!
Connect only to suitable supply voltage (KNX bus
voltage)!
Installation and assembly of electrical equipment
must be in accordance with national building,
electrical and safety codes!
Follow the steps below to install the Thermostat:
1 - Place the plastic base in the mechanism box using the two
screws included in the packaging.
2 - Connect the bus line to the KNX connector (B) respecting the
polarity.
3 - Fit the Thermostat onto the plastic base, forcing it until it is
perfectly tied
COMMISSIONING
The operation of the product is conditioned to the parameterization
carried out by means of the ETS.
The application software can be downloaded from our website:
Follow these steps to start up the Thermostat:
1 - Assign the physical address and set parameters with the ETS.
2 - Press the programming key (A). The green programming LED
(A) will light permanently and is ready for programming.
3 - Load the physical address and the application program into the
Thermostat.
4 - If programming is successful, the green programming LED (A)
turns off, indicating that the actuator is ready to operate.
PROGRAMMING KEY AND LED (A)
In addition to enabling putting the actuator into operation, it is also
useful to inform about a blocking problem of the dimmer, lighting
alternately in red and green.
This can only be due to incorrect programming from ETS.
In case of this problem, it would be necessary to reset the device:
1 - Remove the terminal (B) from the KNX bus.
2 - Press and keep pressing the programming key (A).
3 - Reconnect the terminal (B) to the KNX bus.
4 - Release the programming key (A).
This process will deleteany physical address and application program
saved on the Thermostat.
B
DINUY, S.A. Auzolan, 2, 20303, IRUN, SPAIN
Number
Type
sensor
Light sensor
90mm
- +
46mm
TM KNT 001
WARNING!:
.
www.dinuy.com.
www.dinuy.com
Binaries or Analogs
ST KNT 001 & ST KNT 002
Door Contact: <10m
Temperature Probe: <10m
Accuracy: ±0,4ºC (10ºC bis +85ºC)
0,045Lux bis 188.000Lux
Accuracy: ±4% (0% bis 80%)
P20 according to EN60529
Security 2014/35/EU
EN60669-1, 2-1 & 2-3
14mm
Prog
C C
4
3
2
1
14mm
D
E
F
G
H
Prog
- +
C C
4
3
2
1
Prog
- +
C C
4
3
2
1
TM KNT 002
21 ~ 32V
DC
< 4mA
KNX Bus terminal
ETS5 or later
TP1
System Mode
4 Inputs
-40ºC ~ +100ºC
-40ºC bis +125ºC
0% bis 100%
From 0.0 to 99.9
-5ºC ~ +45ºC
-30ºC ~ +70ºC
EMC 2014/30/EU
KNX Standard 2.0
90mm
13mm
30mm
TM KNT 002
A
C
A

Publicidad

loading

Este manual también es adecuado para:

Tm knt 002