The Eurotech battery charger has been developed based entirely on digital technology and is protected against inversion and overheating.
It can charge 12 and 24 Volt devices (automatic recognition).
The charger is suitable for charging only and exclusively lead GEL, AGM or Liquid Electrolyte (lead acid) batteries when properly set. Do not
attempt to charge other types of batteries. Do not approach the battery with open flames or lit cigarettes. Always charge batteries in ventilated
environments and while battery covers, if exist, are open, to avoid gas buildup. Do not disconnect the battery during charging. The connector
may issue sparks which might cause an explosion. Do not place the charger near flammable objects. Connect the charger to the mains using a
grounded socket. Check the electrolyte level before and after each charge; if necessary top up using only distilled water, do not add acid. Do not
remove the charger cover. In need of assistance, contact authorised personnel only.
SETTING THE DIP SWITCH BASED ON TYPE OF BATTERY TO BE CHARGED AND ITS CHARGING
The DIP switch is placed inside the charger and must be set only by experienced personnel.
CHARGING CURVE
GEL
AGM
LEAD-ACID
*
Factory setting GEL - 15 A
fixed light
RED
blinking
GREEN-RED
alternating
blinking
GREEN
fixed light
ORANGE
blinking
If the battery voltage is 10V or less, the charger will not start. Upon connecting the battery, the LED indicates the set charge curve for 2 seconds,
as follows:
RED
= Lead-acid,
Charging voltage switching is automatic for 12 or 24 Volt: make sure that the voltage of the battery or battery pack is 12 or 24 Volt. DO NOT
charge batteries with different voltages. Before connecting the charger make sure it is properly configured: non-conformant settings can result
in deformation, battery breakage and personal injury.
During charging hydrogen, a most explosive gas, is formed; operate with utmost caution and pay strict attention to the warnings
GENERAL SAFETY WARNINGS
CURRENT.
5
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
LED COLORS
BATTERY CONNECTED
CHARGING (costant current)
CHARGING (costant voltage)
INFINITE OR COMPLETION CHARGING
SUSPENDED CHARGING (overheating)
ERROR
GREEN
= GEL,
ORANGE
= AGM.
CHARGING CURRENT (Amper)
10
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
WARNING!!!
appearing in this manual.
OFF
15
*
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
ON
ON
1 2 3 4 5 6
1 2 3 4 5 6
DIP3: Set to ON by default for
infinite charging (the battery can
always remain connected to the
charger); when set to OFF the
charger will turn off 4 hours after
charging has been completed.
DIP6: Do not modify (used only
during testing).
D O N OT m a ke a n y o t h e r
adjustments, only follow the
instructions in this manual.
GB
ON
20