GB
CASE
Dimensions:
Connection:
iP index:
weight:
DISPLAy
type :
MEASuREMEntS
three-phase (3 or 4 wires), two-phase ( wire) and single-phase networks
VoLtAGE (tRMS)
Direct measurement:
measurement via Pt:
Display and resolution
Permanent overload:
Update period:
CuRREnt (tRMS)
via Ct with:
minimum measuring current
input consumption:
Display:
permanent overload:
intermittent overload:
Update period:
maximum ratio Ki x KU:
PoWER
total:
Update period:
FREQuEnCy
Update period:
AuXILIARy SuPPLy IEC / CE
110 to 400 v aC 50/60 Hz
10 to 350 v DC
1 to 48 v DC
Consumption:
oPERAtInG ConDItIonS
Operating temperature:
storage temperature:
Relative humidity:
96 x 96 x 60 mm
or 96 x 96 x 80 mm with all optional modules (DiN 43700)
via .5 mm
disconnectable terminals
(voltage and others) and 6 mm
iP5 (front panel) and iP30 (case)
400 gr.
Backlighted LCD display
from 18 to 700 v aC (phase/phase)
from 11 to 404 v aC (phase/neutral)
• Primary:
up to 500 kv
• secondary:
60, 100, 110, 115, 10, 173 and 190 v aC
from 0 to 500.0 kv
760 v aC
1 second
• Primary:
up to 9995 a
• secondary:
1 or 5 a
10 ma
< 0.3 va
from 0 to 11 ka (1.1 times the primary value)
10 a
10 in / 1 second
1 second
10 000 000
0 to 8000 mw/mvar/mva
1 second
from 45,0 to 65,0 Hz
1 second
± 10 %
± 0 %
-6 % / + 0 %
< 10 va
-10° to + 55°C (14° to 131°F)
-0° to + 85°C (-4° to 158°F)
95 %
TEchNIcAl chARAcTERISTIcS
fixed terminals (current)
146 69 - Ref.: N9511/00
146 69
53