The following parameters can be set in this way
S S E E T T
T T e e m m p p e e r r a a t t u u r r e e s s e e t t p p o o i i n n t t
The target temperature for the refrigerator.
H H A A L L
U U p p p p e e r r a a l l a a r r m m p p o o i i n n t t
The maximum permissible inside temperature. An alarm is triggered when this value is reached.
L L A A L L
L L o o w w e e r r a a l l a a r r m m p p o o i i n n t t
The minimum permissible inside temperature. An alarm is triggered when this value is reached.
M M U U D D
M M u u t t e e s s w w i i t t c c h h p p e e r r i i o o d d
When there is an alarm, the audible signal can be switched off for a specified period of time by pressing the
key. The specified period is defined by this parameter. It can be varied between 0 and 60 minutes in 1-
minute increments.
C C / / F F
U U n n i i t t o o f f t t e e m m p p e e r r a a t t u u r r e e
Conversion of the temperature display from °C (Celsius) to °F (Fahrenheit).
T T I I M M
C C l l o o c c k k
The current local time. The time starts at 00:00 hours when the unit is switched on. First set the minutes by
means of the
and
the
key again to save the new time.
L L A A N N
L L a a n n g g u u a a g g e e
This parameter is used to set the language in which the warnings and error messages are displayed. ENG
for English is preset. The alternatives are: ESP for Spanish, POR for Portuguese. FRA for French, DEU for
German, BHM for Bahasa (Malaysia), NED for Dutch, SVE for Swedish, SUO for Finnish, NOR for Norwegian,
ITA for Italian or DAN for Danish.
A A D D R R
N N e e t t w w o o r r k k a a d d d d r r e e s s s s
Several units can be networked by means of the built-in RS485 interface. In this situation, each individual unit
must have a separate address. This address is defined by the ADR parameter.
POWER FAILURE
In the event of a power failure, the red POWER FAIL LED flashes and an audible
alarm sounds. The audible alarm can be muted for a certain period of time (MUD
parameter) by pressing the
After a certain interval, the display switches off automatically. However, the inside
temperature can be displayed again by pressing the
No parameters can be changed during a power failure.
If, during a power failure, the inside temperature increases beyond the upper alarm point, the temperature
alarm is displayed and the corresponding values are stored in the Alarm History.
An alarm caused by a power failure is not signalled by the external alarm function. Should this be necessa-
ry, this function can be added later. Please contact your service centre for this.
keys. Once the
key has been pressed, the hour setting can be changed. Press
key.
8
key.