DIP-SWITCH CONFIGURATION

SETTINGS
To be done in the installation phase, only by expert personnel.
Some functions are not compatible with each other and, for
this reason, limits to Dip-Switch configurations have been set.
By turning on or off Dip-Switches inside the thermostat, we
get the following functions:
Sw1 Dip 1 (Default OFF)
Water valve fitted:
- Present, set (ON).
- Absent, set (OFF).
Sw1 Dip 2 (Default OFF)
Position of the water temperature probe:
- Water temperature probe positioned up line from the valve,
set (ON).
- Water temperature probe positioned down line from the
valve, set (OFF).
Sw1 Dip 3 (Default OFF )
Water valve management:
- Optimised, set (ON).
heating mode: valve closure delayed compared to the
turning off of the ventilation;
cooling: valve closure earlier than the turning off of the
ventilation.
- Normal, set (OFF).
Sw1 Dip 4 (Default OFF )
Probe adjustment:
- Fixed adjustment, set (ON).
- Dynamic correction, set (OFF),
calculated on the basis of the water temperature.
NOTES:
* = In the fan coils with two valves installed in four-pipe systems the installation of a PLASMACLUSTER
- For the proper functioning of the SA room probe make sure that the
Sw2
Sw1
JP1
ON
Sw1
OFF
8
Water valve present
Water probe upline from the valve
Optimised water valve management:
Fixed sensor correction
1 2 3 4
5
Dynamic Probe Correction
Normal water valve management:
Water probe downline from the valve
Water valve not fitted
Sw1 Dip 5 (Default OFF)
Heating mode enabling temperature:
- Reduced, set (ON).
Minimum water temperature 35 °C
- Normal, set (OFF).
Minimum water temperature 39 °C.
Sw1 Dip 6 (Default OFF)
Cooling mode enabling temperature:
- Reduced, set (ON).
Maximum water temperature 22°C
- Normal, set (OFF).
Maximum water temperature 17°C
Sw2 * Dip 1 (Default OFF)
Selection of the type of plant in which the fan coil is included:
- Four-pipe system, set (ON).
- Two-pipe system, set (OFF).
Sw2 * Dip 2 (Default OFF)
Presence of PLASMACLUSTER
- Present, set (ON).
- Absent, set (OFF).
Sw2 Dip 3 (Default ON)
Air temperature probe enabling:
- Internal control panel probe,set (ON).
- Probe in fan coil, set (OFF).
Sw2 Dip 4 (Default OFF)
Option not available
is in ON position and the jumper at INT. position.
Sw2Dip3
Minimum water temperature 35°C in heating mode
Maximum water temperature 22°C in cooling mode
*
Four-pipe system
*
PLASMACLUSTER
Internal command panel sensor
1 2
6
3 4
Probe in the fan coil
*
PLASMACLUSTER
*
Two-pipe system
Maximum water temperature 17 °C in cooling mode
Minimum water temperature 39 °C in heating mode
®
air purifier:
®
air purifier is not allowed.
®
present
Option not available
Sw2
Factory setting
®
not fitted