1. Download the latest firmware version and Device Management Utility (DMU) from the
SurgeX website:
2. Enable the upgrade feature. Use the CLI set upgrade enable yes command via telnet, or check the
"Upgrade Enable" box on the Device web page.
3. Run the DMU. If the AR you would like to upgrade is not visible in the list box, either:
•
Select Device | Discover from the menu to locate the ARs on the local network.
•
Select Device | Add from the menu to manually add the AR by IP address.
Once the device is displayed in the list, highlight it.
4. Select Manage | Upgrade Firmware.
Enter User Name admin and the password for the Administrator.
Enter the filename of the new firmware, or click Browse and navigate to the firmware file to be used. AR
firmware files use the file extension .g2u. If no files of that type are displayed, ensure that the "Files of Type"
box is set for SX-iPD or All Files.
Click OK when all details are entered.
5. The upload will begin, and a progress bar will be displayed.
6. When the firmware upload is complete, the AR will automatically reboot and will be ready for use.
IX. Reset Button
The recessed reset pushbutton located on the front panel performs 3 functions as
detailed below:
Action
Momentary
5 Second Push
Hold while
powering up
© AMETEK Electronic Systems Protection, Inc. | Technical Support: 800-645-9721 | surgex.com
http://www.surgex.com.
Result
Soft Reset. Will not affect outlet state.
Reset to Factory Defaults. Hold until the "System On" LED is blinking,
then release.
Recovery Mode. Allows upload of new firmware to the current IP address.
SA-82-AR
User Manual