• Connect drain pipe
directly to drain piping connecting part (socket side) of
B
drain hose
.
• Be sure to connect drain hose
to the indoor unit side as shown in the illus-
tration on the right. Be sure to connect the drain hose connecting part using
adhesive of polyvinyl chloride family to prevent leakage.
• To bring up the drain exit, first arrange drain hose to go upward vertically,
and then provide 1/100 or more downward slope, as shown in the illustration
below.
Drain piping connecting part
Drain hose
Drain hose
connecting part
• If the drain piping pass indoor, be sure to apply insulating material
polyethylene, specific gravity 0.03, thickness more than 3/8 in. (10 mm)).
Connect drain hose connecting part using adhesive of polyvinyl chloride family
before installing the hose band.
• Apply insulating material
J
until drain piping connecting part, as shown in the
upper right illustration.
• Drain piping should form a downward slope (1/100 or more) to the outdoor
drain exit. Do not form trap or raise the pipe.
• Do not arrange the pipe horizontally for more than 65 ft. (20 m). When the drain
piping is too long, use support metal to prevent the drain pipe from forming
an up or down curve. Be sure not to install a air bleeder. (Since drain lift-up
mechanism is built-in, drain may blow out.)
• Odor trap for drain outlet is not necessary.
• For grouped piping, arrange piping so that the grouped piping is about 3-15/16
in. (100 mm) lower than the unit drain exit, as shown in the figure. Use about
a drain pipe (O.D. 1-1/2 in. (38 mm)) for grouped piping, and arrange it so that
it forms about 1/100 or more downward slope.
• Do not place drain piping directly into a place where ammonia gas or sulfuric
gas is formed, such as sewage tanks or septic tanks.
Drain pipe
B
Drain hose
1/100 or more
downward slope
* Drain hose
can be cut by
tools such as cutters.
2-3/8 in.
Ceiling
(61 mm)
(Foamed
J
Drain hose
Drain hose connecting part
2-3/8 in.
(61 mm)
Drain pipe
B
Pipe elbow
* Do not make drain
piping as shown.
Ceiling
2 to 5 ft.
(0.75 m to 1.5 m)
Insulating
material
J
1/100 or more downward slope
Air bleeder
As long as possible
As short as possible
(about 4 in. (100 mm))
Drain piping connecting part (with socket)
Drain pipe
1/100 or more downward slope
Drain piping connecting part
Drain hose
Insulating material
Drain piping con-
necting part
About 2-3/8 in. (60
Drain pipe
mm) from the end
• Insert the drain pipe
completely into drain
B
piping connecting part.
• Apply insulating material
until drain piping
J
connecting part, as shown above.
Hose band
Support metal
As much as possible
(about 4 in. (100 mm))
Tip of drain hose
Do not raise
dipped in water
At least 2 in.
(50 mm) gap
Odor trap
1/100 or more
downward slope
Drain pipe
(O.D. 1-1/2 in. (38 mm))
B
J
B
EN-6