MODELS: ETW2CP, ETW3CP
Installation and Setup Instructions
WARNING
Risk of Fire or Electric Shock
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• More than one circuit breaker or disconnect switch may be required to de-energize the equipment before servicing.
• For plastic enclosures, bonding between conduit connections is not automatic and must be provided as part of the installation.
• Installation and/or wiring must be in accordance with National and Local Electrical Code requirements.
• Use #14-#8 AWG wires, rated at least 105° C - COPPER conductors ONLY.
• If the power disconnect point is out of sight, lock it in the OFF position and tag it to prevent unexpected application power.
• Make sure there is no wire insulation under the terminal plate on the time switch connector. Firmly tighten terminal screws.
• For outdoor locations or wet locations (rain-tight), conduit hubs that comply with requirements of the UL514B (standard for fitting conduit
and outlet boxes) are to be used.
• Do NOT exceed maximum current carrying capacity.
• KEEP DOOR CLOSED AT ALL TIMES when not servicing.
NOTICE
• Do NOT touch circuit board components, contact can create a static discharge, which can damage these electronic components.
Description
Intermatic ETW2CP and ETW3CP Smart Timers offer a multi-
purpose solution for indoor and outdoor load control
applications. Available in a 2-circuit and 3-circuit configuration,
these controls provide flexible 365-day, Astronomic, and
Holiday programming options.
Once onboarded to a wireless network, the ETW2CP/ETW3CP
can be controlled using the Intermatic Connect app, available
via Google Play and the App Store. Units can be field
configured for either single-pole or double-pole applications
and be used for 120-277 VAC. The controls also include
terminal locations for line voltage overrides.
Federal Communications Commission (FCC) Notice for ETW Series Wi-Fi Timers
This device complies with part 15 of the FCC rules. Operation of this device is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) This device must accept any interference, including interference that may cause undesired operation. This equipment
has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses and radiates radio frequency energy and, if not installed and used in accordance with instructions, may cause harmful interference
to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference that requires the user to correct
at his or her own expense.
ETW3CP
Intermatic Connect 365-Day
Programmable Smart Wi-Fi Timer
Ratings
Electrical Specifications
Operating Voltage
Remote Inputs
Load Rating (Motor)
FLA
Power Consumption
Electronic Ballast
General Purpose
Current Rating
Impulse Voltage
Overvoltage Category
Pollution Degree
Operating Temperature
Control Construction
Enclosure Type
Dimensions H x W x D
120-277 VAC, 50/60 Hz
120-277 VAC, 50/60 Hz
1 HP 120 VAC (NO)
2 HP 240 VAC (NO)
16 A FLA, 96 A LRA, Type 1C @ 120 VAC 50/60 Hz (NO)
15 A FLA, 96 A LRA, Type 1C @ 240 VAC 50/60 Hz (NO)
7 W
16 A per circuit (NO)
30 A (NO)
10 A (NC) @ 55° C, 5 A (NC) @ 70° C
4000 VAC
III
3
-40º C to 70º C
Independently Mounted
Type 3 Indoor/Outdoor Enclosure
7 1/2" x 8 7/8" x 3"