Descargar Imprimir esta página

Victron energy MultiPlus 12/3000/120-16 230V Manual página 25

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 99
8. Technical specifications
MultiPlus
PowerControl / PowerAssist
AC input
Maximum feed through current (A)
Minimum AC supply current capacity
for PowerAssist (A)
INVERTER
Input voltage range (V DC)
Output
(1)
Cont. output power at 25 °C / 77 °F (VA)
(3)
Cont. output power at 25 °C / 77 °F (W)
Cont. output power at 40 °C / 104 °F (W)
Cont. output power at 65 °C / 150 °F (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
Zero-load power in AES mode (W)
Zero-load power in Search mode (W)
CHARGER
AC Input
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A)
Charge current starter battery (A)
Battery temperature sensor
GENERAL
Auxiliary output
Programmable relay
(5)
Protection
(2)
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
230 V AC-connections
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
Automotive Directive
1) Can be adjusted to 60 Hz; 120 V 60 Hz on request
Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230 VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) At 25 °C ambient
5) Programmable relay which can be set for general
alarm, DC undervoltage or genset start/stop function
AC rating: 230 V/4 A
DC rating: 4 A up to 35 VDC and 1 A upto 60 VDC
12/3000/120-16 230V
12/3000/120-50 230V
Input voltage range: 187-265 VAC
9,5 – 17
Output voltage: 230 VAC ± 2 %
3000
2400
2200
1700
6000
93
20
15
8
Input voltage range: 187-265 VAC
14,4
13,8
13,2
120
(4)
Max. 16A Switches off when no external AC source available
Operating temp.: -40 to +65 °C (-40 – 150 °F) (fan assisted cooling)
Material & Colour: aluminium (blue RAL 5012) Protection category: IP 20, pollution degree 2, OVC3
24/3000/70-16 230V
24/3000/70-50 230V
Yes
Input frequency: 45 – 65 Hz
16 / 50
2,3 / 5,3
19 – 33
Frequency
3000
2400
2200
1700
6000
94
20
15
10
Input frequency: 45 – 55 Hz
Power factor: 1
28,8
27,6
26,4
70
4 (12 V and 24 V models only)
Yes
Yes
a - g
Humidity (non-condensing): max 95 %
M8 bolts (2 plus and 2 minus connections)
Screw terminals 13 mm² (6 AWG)
19
362 x 258 x 218
EN 60335-1, EN 60335-2-29, IEC62109-1
EN 55014-1, EN 55014-2, EN 61000-3-3
2004/104/EC
48/3000/35-16 230V
48/3000/35-50 230V
38 – 66
50 Hz ± 0,1 %
:
3000
2400
2200
1700
6000
95
25
20
12
57,6
55,2
52,8
35
23

Publicidad

loading