8.1
Operating conditions
The stated outputs of the units are obtained under the reference conditions outlined in ISO 8528-1(2005):
Total barometric pressure: 100 kPa - Ambient air temperature: 25°C (298 K) - Relative humidity: 30%.
The unit's output is reduced by approximately 4% for every additional 10°C and/or approximately 1% for every additional 100m in
altitude. Units can only operate while stationary.
8.2
Capacity of the generating set
Before connecting and operating the unit, calculate the electrical power required by the units to be used (in watts)*. To ensure
optimal operation, the total wattage of all equipment used at the same time must be:
-
greater than 60% of the rated load for the unit (risk of insufficient load);
-
less than the rated load for the unit during continuous operation (risk of overload).
If the unit is run under or over its rated load frequently or for long periods of time, it can start to wear very quickly. Damage caused
in this way will not be covered by the warranty.
*
This load is usually indicated in the technical specifications or on the manufacturer's plate for the equipment. Some equipment requires a higher
load when starting. This minimum required power must not exceed the unit's maximum power
8.3
Generating set identification
The identification plate for the unit (example shown below) is affixed inside one of the skirts or on the chassis.
(N)
(B)
Serial numbers will be required when requesting troubleshooting advice or spare parts. For your records, please enter the unit and
engine serial numbers below.
Unit serial number:
....../.............. - ........................... - .........
8.4
Specifications
Model
Maximum power
Rated power
Acoustic pressure at 1 m
Acoustic measurement uncertainty
Engine type
Maintenance kit
Recommended fuel
Fuel tank capacity
Recommended oil
Oil sump capacity
Oil cut-out*
Direct current
Alternating current
Circuit breaker(s)**
Socket type
Type of spark plug
Dimensions l x w x h
Weight (without fuel)
o: standard
*Oil cut-out: If there is no oil in the engine sump or if the oil pressure is low, the oil cut-out mechanism automatically stops the engine to prevent any
damage. If this occurs, check the engine oil level and top it up if necessary before looking for any other cause of the problem.
**Circuit breaker: The set's electrical circuit is protected by one or more magnetothermal, differential or thermal cut-out switches. In the event of an
overload and/or short circuit, the supply of electrical energy may be cut.
If necessary, replace the circuit breakers in the generating set with circuit breakers which have identical nominal ratings and specifications.
1114_EN
(A)
(D)
(E)
(H)
(F)
(I)
(G)
(M)
(c)
PERFORM
PERFORM
3000 XL C5
4500 XL C5
(RCD)
2800 W
2400 W
81 dB(A)
0,46 dB(A)
CH270_C5
CH395_C5
RKS1
Unleaded
petrol
13 L
10W30
0,60 L
O
X
230V-10,4A
230V-13,9A
O
2 x 2P+T
230V-10/16A
230V-10/16A
330830012
330830012
65 x 51 x 46
81 x 55,5 x
cm
46,5 kg
X: not available
.
(A):
Model
(B):
CE/EAC marking
(C):
Guaranteed acoustic
(J)
power level
(K)
(D):
Maximum power
(L)
(E):
Nominal power
(F):
Power factor
Engine brand:
(e.g. Kohler)
........................................
PERFORM
4500 XL AVR
(RCD)
C5 (RCD)
4000 W
4000 W
3200 W
3200 W
82 dB(A)
82 dB(A)
0,34 dB(A)
0,34 dB(A)
CH395_C5
RKS2
RKS2
Unleaded
Unleaded
petrol
petrol
18 L
18 L
10W30
10W30
1,10 L
1,10 L
O
O
X
X
230V-13,9A
O
O
2 x 2P+T
2 x 2P+T
230V-10/16A
330830012
81 x 55,5 x
59 cm
59 cm
66,5 kg
72,5 kg
23/204
Section 8. Technical specifications
(G):
Ground
(H):
Current amperage
(I):
Current frequency
(J):
Electrical voltage
(K):
Protection rating
(L):
Reference standard
(M):
Serial number
(N):
UKCA marking
Engine serial number:
(e.g. Kohler (SERIAL NO. 4001200908))
......................................................
PERFORM
PERFORM
5500 T XL C5
6500 XL C5
(RCD)
(RCD)
4500 W
6300 W
3200 W
5200 W
82 dB(A)
83 dB(A)
0,34 dB(A)
0,40 dB(A)
CH395_C5
CH440_C5
RKS2
RKS2
Unleaded
Unleaded
petrol
petrol
18 L
18 L
10W30
10W30
1,10 L
1,29 L
O
O
X
X
400V-4,6A
230V-22,6A
O
O
1 x 2P+T
1 x 2P+T
230V-10/16A
230V-10/16A
- 1 x 3P+T+N
- 1 x 2P+T
400V 16A
230V 32A
330830012
330830012
81 x 55,5 x
81 x 55,5 x
59 cm
59 cm
76,5 kg
87 kg
PERFORM
7500 T XL C5
(RCD)
6500 W
5200 W
83 dB(A)
0,40 dB(A)
CH440_C5
RKS2
Unleaded
petrol
18 L
10W30
1,29 L
O
X
400V - 7,5A
O
1 x 2P+T
230V -10/16A
- 1 x 3P+T+N
400V 16A
330830012
81 x 55,5 x 59
cm
94,5 kg
2021-07-17