MODELS WITH BATTERY CHARGER
INPUT
Nominal voltage
Accepted range
Nominal frequency
(2)
Maximum current
(3)
Nominal current
BATTERY
Nominal voltage
Nominal Ah
End of charge voltage
No. of batteries / V / Ah
(4)
Recharge time
VARIOUS
(5)
Ambient temperature
Humidity
Protections
Safety compliance
EMC compliance
Dimensions H x L x W
Weight
BASIC MODELS
BATTERY
Nominal voltage
Nominal Ah
End of charge voltage
No. of batteries / V / Ah
VARIOUS
(5)
Ambient temperature
Humidity
Protections
Safety compliance
EMC compliance
Dimensions H x L x W
Weight
(1)
the symbol "-" replaces an alphanumeric code for internal use
(2)
@ minimum voltage of 190Vac, batteries charging
(3)
@ nominal voltage of 230Vac, batteries charging
(4)
Time required to reach 90% of the charge (after a full discharge)
(5)
20-25°C for longer battery life
(6)
Corresponding to: 19" x 4U x 26" (H x L x D)
T
ECHNICAL DATA TABLE
(1)
BX02C192012--
(1)
BX02K192012--
[Vac]
[Vac]
[Hz]
[A]
[A]
[Vdc]
[Ah]
[Vdc]
16 / 12 / 12 (High Current Discharge Capability)
[h]
[°C]
< 90% non-condensing
overcurrent – short circuit - overvoltage
EN 50091-1-1 and directive 73 / 23 / EEC, 93/68 EEC
EN 50091 - 2 cl. B and directive 89/336 EEC, 92/31 EEC,
[mm]
455 x 175 x 660
[Kg]
(1)
BX02P192007--
(1)
BX02V192007--
[Vdc]
[Ah]
7
[Vdc]
16 / 12 / 7 (High Current
Discharge Capability)
[°C]
< 90% non-condensing
overcurrent – short circuit
EN 50091-1-1 and directive 73 / 23 / EEC, 93/68 EEC
EN 50091 - 2 cl. B and directive 89/336 EEC, 92/31 EEC,
[mm]
455 x 175 x 660
[Kg]
60
40
220 / 230 / 240
190 ÷ 276
50 - 60
2
1,7
192
12
219,2
8 ÷ 10
0 – 40
93/68 EEC
(6)
80
(1)
BX02P192012--
(1)
BX02V192012--
192
12
219,2
16 / 12 / 12 (High Current
Discharge Capability)
0 – 40
93/68 EEC
(6)
80