Ground Continuity Monitoring (GCM)
When the Legrand Ground Continuity Monitoring (GCM) device is utilized in lieu
of an ordinary wiring device, the GCM provides an easy and continuous indication
of wiring polarity and ground continuity of extension cord sets and wall receptacles
that will reduce most of the testing, record keeping and documentation on cord sets
and wall receptacles for compliance with OSHA's Assured Equipment Grounding
Conductor Program.
When Ground Continuity Monitoring (GCM) extension cord set or plug is plugged
into any receptacle or connector of a conventional cord set, the Ground Continuity
Monitoring (GCM) device will provide one of the following indications:
1. Blue LEDs will illuminate with proper ground conductor continuity and correct
Hot/Neutral wiring polarity.
2. Red LEDs will illuminate with broken ground continuity or reversed Hot/Neutral
wiring polarity.
3. No LEDs illuminated indicate no power or open Hot, open Neutral, or reversed
Hot/ Ground wiring polarity.
Once plugging the GCM device into any receptacle and utilizing it to provide power
for drills, saws, etc., the GCM device offers an immediate check on the above
conditions, thus eliminating frequent testing and record keeping on extension cord
sets and wall receptacles.
If the Blue LEDs are not illuminated – the employee should call an electrician to
check the circuit for malfunction.
The GCM devices monitor for ground continuity and proper Hot/Neutral wiring
polarity. It does not monitor the quality of the ground and power connections in the
branch circuit.
Note: GCM plugs and connectors will monitor only one direction – through the cord
set to the power – not to the appliance or load side.
Do not use a GCM of any other manufacturer in the same circuit or questionable
indications may result.
Surveillance de continuité de masse
Lorsque le produits Surveillance de continuité de masse (GCM) de Legrand sont
utilisés, au lieu des prises régulières, le GCM fournit une indication continuelle de la
polarité du câblage et de la continuitée de la mise à la terre des cordes d'extension
et des réceptacles muraux, ce qui réduit considérablement la période de test, la
tenue des résultats et la documentation afin de rencontrer les exigences de OSHA du
programme d'assurance de la fuite à la terre des équipements.
Lorsque les cordes d'extension ou les prises GCM, sont branchées dans un
réceptacle ou au connecteur d'une corde d'extension conventionnelle, le module
GCM, fournira une des indications suivantes:
1. L DEL bleu s'illuminera lors de la présence d'une bonne continuité de la mise à la
terre et d'une bonne polarité phase /neutre.
2. Le DEL rouge s'illuminera lors d'un manque de continuité de la mise à la terre ou
lors d'inversion de la polarité phase /neutre.
3. Si aucun DEL s'illumine, ceci indique l'absence d'alimentation ou que la phase ou
le neutre sont ouverts ou une inversion de polarité entre la phase /mise à la terre.
Une fois que le module GCM est branché dans un réceptacle et utilisé afin d'alimenter
un appareil tel que perceuse, scie, etc., le module donne une vérification immédiate
de toutes les conditions énumérées ci-dessis, éliminant les vérifications réglières
et fréquentes ainsi que la tenue des résultats sur les cordes d'extensions et les
réceptacles muraux.
Pass & Seymour
Watertight Ground Continuity Monitoring (GCM) Plugs & Connectors
Bouchons et connecteurs pour surveillance de continuité de masse (GMC) étanche
Enchufes y conectores del Monitoreo de continuidad de conexión a tierra
(GCM) hermético
Installation Instructions • Notice d'installation • Instrucciones de instalación
Wiring Instructions: Ground Continuity Monitoring (GCM)
1. Remove plug/connector insert from rubber housing.
2. Do not pre-strip cord jacket or conductors, insert cord through clamp assembly
and rubber housing, or nut, ferrule, grommet and rubber housing. Strip the cord
jacket 1". Strip all three (3) conductors per strip gauge (7/8") and twist leads to
eliminate frayed ends.
3. Make sure all three (3) terminal screws are BACKED OUT TO FULLEST
POSITION (do not use excessive force) so that terminal wire nut is past wire
entrance hole so that conductor leads may pass through unobstructed.
Insert stripped conductors into individual wiring pocket. Green screw for green
grounding wire, white (silver) screw for white neutral wire and brass (yellow) screw
for black hot wire. Tighten each screw as each conductor is inserted. Use 12-15
in-lbs. torque.
4. Push plug /connector insert into rubber housing. Tighten (3) insert assembly
screws. Tighten (2) cord clamp assembly screws or cord grip nut until cord is
securely restrained in place.
5. Plug Ground Continuity Monitor cord set or plug into any receptacle with known
good ground and observe LEDs as being on...ensuring proper wiring before use
of cord set or appliance.
6. Straight blade devices can accommodate cord diameters from 0.37" to 0.61" (SJ'
cable 16/3 - 10/3 and S' cable 18/3 - 12/3) turn lock devices can accommodate
cord diameters from 0.45" to 0.69" (SJ' cable 14/3 - 10/3 and S' cable 16/3 - 12/3).
INSTRUCTIONS EN FRANÇAIS
Si le DEL bleu ne s'illumine pas – l'employé devrait téléphoner un électricien afin de
fair vérifier le mauvais fonctionnemet du circuit.
Le module GCM supervise la continuité de la mise à la terre et la bonne polarité
phase/neutre. Il ne surveille pas la qualité de la misa à la terre et des circuits de
puissance.
Note: Les prises et connecteurs GCM vont surveiller dans une direction seulement –
de la corde d'extension vers la source de puissance – et non de lar corde d'extension
vers l'appareil ou la charge.
Ne pas utiliser un module GCM d'un autre manufacturier dans le même circuit, un
résultat aléatoire pourrait s'en suivre.
Instructions de cablage : Surveillance de continuité de masse
1. Retirez l'intérieur de la prise/connecteur de son boîtier de caoutchouc.
2. Ne pas dégainer le câble ni ses conducteurs, insérez le câble à travers la pince
de retenue ainsi que l'écrou, férule, oeillet et le boîtier de caoutchouc. Dégainez
l'isolant du câble de 1 pouce. Dégainez les (3) trois conducteurs selon le gabarit
(7/8 pouces) et tourner le bout des brins de chacun des conducteurs pour éliminer
l'effilochage.
3. Assurez-vous que les vis des trois terminaux sont COMPLÈTEMENT
DÉVISSÉES (ne pas utilisé une force excessive) afin que les brins de chaque
conducteur ne soient endommagés lors du brancement.
®
14W47GCM
BLUE = OK
BLEU = OK
AZUL = OK
RED = DO NOT USE
ROUGE = NE PAS UTILISER
ROJO = NO USAR

Publicidad

loading

Resumen de contenidos para LEGRAND Pass & Seymour 14W47GCM

  • Página 1 Ground Continuity Monitoring (GCM) Wiring Instructions: Ground Continuity Monitoring (GCM) When the Legrand Ground Continuity Monitoring (GCM) device is utilized in lieu 1. Remove plug/connector insert from rubber housing. of an ordinary wiring device, the GCM provides an easy and continuous indication 2.