Sensors to be displayed
It defines which probe will be displayed on the screen (probe 1, probe 2 or probe 3).
Display mode
It defines the information displayed on the screen during normal operation:
Probe and clock: It displays the probe defined in the Sensors to be displayed parameter, the date, time
Ÿ
and day of the week.
Probe and text: It displays the probe defined in the Sensors to be displayed parameter and the
Ÿ
description of the unit.
Probes, clock and text: It displays all the active probes, date, time and day of the week and the description
Ÿ
of the unit . The configuration of the Sensors to be displayed does not intervene in this mode.
Display unit
It defines the temperature display units (º Centigrade or º Fahrenheit).
Probe setting
It defines the function of the inputs of probe S1 and S3, the function of the S2 input is not configurable.
TEM at S1/REG at S3: The temperature control, alarms and HACCP probe (Probe 1) is connected to the
Ÿ
S1 input and the temperature data logger probe (Probe 3) to the S3 input:
TEM at S1/REG at S3 (According to EN 12830)
S 1
S 2
CON4
If probe 3 is configured as 2 defrost, the data logging deactivates.
TEM and REG at S3: The temperature control, alarms and HACCP probe is also the data logger probe
Ÿ
(Probe 1) and it is connected in input S3, the product temperature probe is connected in the S1 input.
TEM and REG at S3
S 1
S 2
CON4
Decimal point
It defines is the degree's decimal points are displayed or not, and therefore the resolution of the unit.
u
Date
If configures the current date (year, month, day).
Hour
If configures the current time (day of the week, day, minute).
S 3
Probe 1 (Control of temperature, alarms and HACCP)
Probe 2 (Defrost / 2nd defrost)
Probe 3 (Data logger / 2nd defrost)
S 3
Probe 3 (Product temperature probe / 2nd defrost)
Probe 2 (Defrost / 2nd defrost)
Probe 1 (Control of temperature, alarms, HACCP and data logger)
21