4 Technical Reference
4.1 Environmental requirements
Parameter
Operating temperature
Storage temperature
Operating humidity
Storage humidity
Maximum altitude
Pollution degree
4.2 IP rating
Degree of protection, IP20
Code
Description
IP
Ingress Protection
2
Protection against solid objects:
• Finger or similar objects not greater
than 80 mm in length
• Solid objects greater than 12.5 mm in
diameter
0
No protection against ingress of water
4.3 Electrical data
In a system, it is the backplane supply module that
receives input power from a local power supply or
from an external backup battery. The power is then
distributed to the other modules through the back-
plane.
The external power supply unit must fulfill protection
class II according to IEC 61140.
Parameter
Voltage, external power
supply
Maximum power, exter-
nal power supply
Voltage, external backup
battery
Maximum power, exter-
nal backup battery
Supply voltage tolerance +12 – +30 VDC
4.4 Terminals
For images, see the appendix.
4
Value
-20°C – +60°C (-4°F –
+140°F)
-40°C – +85°C (-40°F –
+185°F)
20 – 85% relative humid-
ity, non-condensing
10 – 95% relative humid-
ity, non-condensing
2000 m (6562 ft)
2
Value
+ 24 V
96 W
+ 12 V
90 W
No. Terminal
Description
1
+ Power supply
• 12-30V DC
• Protected up to 60V DC in-
12–30 VDC
2
+ Output power to external
equipment
• Output voltage: 24V DC ±
24V/≤1A
• Short circuit protection
• Reverse current protection
3
+ Backup battery
• Battery chemistry: Lead-
• Nominal battery voltage:
12V
• Supported battery capaci-
• Battery charge current:
4
Connection
Power and signal interface to
to back-
first backplane
plane
5, 6 Ethernet
RJ45
10BASE-T, 100BASE-TX
Communication to local HMI
or to service tool
7
Fuse 10 A, for backup battery
Breaking capacity: minimum
1000 A
Voltage: 32 V
Type: mini blade
4.5 LED indicators, backplane supply
module
LED
Color
Green
Power sup-
ply to back-
plane
Red
Unlit
put
5%, max 1A
acid
12V
ty: 2.2Ah - 12Ah
0.88 A
Indication
• The internal supply
voltage is in range
• The system is pow-
ered from an external
power supply unit or
backup battery
• The internal supply
voltage is out of
range
• The system operation
is not guaranteed
• There is no input
power and the bat-
tery voltage is below
9.5 V
• There is no battery
connected