Installation Instructions - Lever Push-In Wire Connectors
Models L2, L3 & L5
• Do not exceed the rating of these connectors
• Turn OFF power before removing or installing connectors
• Wiring must comply with all applicable electrical regulations
• COPPER TO COPPER ONLY. Do not use on aluminium wire.
• Incorrect use of these connectors can cause electrical fires, personal injury or death
• Use only one conductor per port
• Strip wires back 11-12mm
• For solid and rigid stranded wire, grip wire firmly and insert conductor into open port
(lever does not need to be open)
• For flexible stranded wire (>7 strands) lift lever and insert conductor into open port. Close lever
• Verify conductors are fully inserted to the back of the connector.
• To remove a wire, lift lever and pull out wire
Strip Length
Specifications
Rating
Depth
Width
Height
Wire Combination Range
Insertion
Solid and Rigid Stranded
Flexible Wires
Model L2 2-Port
13.3 mm
idealind.com
Removal
Model L3 3-Port
32 Amp / 450V / 85°
18.6 mm
18.9 mm
8.8 mm
0.2mm
- 4.0mm
2
2
0.14mm
- 4.0mm
2
2
Model L5 5-Port
30.4 mm
3/5