WaveLinx
WaveLinx Area Controller
LED Indicators
The LED indicators can be used for diagnostics
and troubleshooting diagnostics of the WaveLinx
Connected Lighting System.
The table below gives you more information.
LED
Green LED ON/Flashing
Connection Port LEDs
Orange LED ON/Flashing
OFF
Solid BLUE
OFF
Power/Health LED
Blinking BLUE
OFF
WAN LED
Solid GREEN
Blinking GREEN
OFF
LAN LED
Solid GREEN
Blinking GREEN
OFF
Solid BLUE
Wi-Fi LED
Blinking BLUE
PAN LED (BT)
OFF
Solid BLUE
OFF
802.15.4 LED
Blinking BLUE
IB503099ML page 6
May 2024
Color/Pattern
The WaveLinx Area Controller 2 is connected to the Ethernet and is connected to a
10/100Mb network.
The WaveLinx Area Controller 2 is connected to the Ethernet and is connected to a
Gigabyte network.
There is no connection to the Ethernet
The WaveLinx Area Controller is powered and operational.
There is no power on the PoE connection or, if power is verified, the WAC2 is unable
to boot due to a system error.
• Short single blink then OFF: This occurs approximately 10-15 seconds after initial
powerup or reboot.
• 50ms ON/50ms OFF repeated: This occurs while the WAC2 is rebooting.
• Flash three times 50ms ON/50ms OFF followed by 2 seconds OFF and then
repeated: The WAC2 has received a firmware file and a firmware upgrade to the
WAC2 is in process.
• 2 seconds ON/2 seconds OFF repeated: The WAC2 is performing firmware
upgrades in connected devices.
Normal condition in stand-alone use. If used in a WaveLinx CORE system, the WAC2
has lost its connection to WaveLinx CORE.
The WaveLinx Area Controller is connected to s WaveLinx CORE system.
The WAC2 is performing a data sync with the connected WaveLinx CORE system.
There is no connection from the building LAN, or the connection has been disabled or
failed.
The WaveLinx Area Controller is connected to the building LAN, has a static or
dynamically assigned IP address, and is ready to communicate.
The LED will blink 1 second ON/ 1 second OFF repeated when the WAC2 is in pairing
mode.
The Wi-Fi Access Point or Client have been disabled.
The Wi-Fi Access Point has been enabled. The Wi-Fi Client is disabled.
• Slow blink (1 second ON/1 second OFF repeated): The Wi-Fi Client is enabled and
has an IP address. The Wi-Fi Access Point is disabled.
• Fast blink (250ms ON/250ms OFF repeated): Wi-Fi Access Point and Wi-Fi Client
are both enabled and available.
LED should be OFF. This functionality is not currently in use.
The 802.15.4 network communication is normal.
The 802.15.4 network is not functional. The 802.15.4 LED should not be OFF. Verify
unit is powered and has had time to fully power up (approx. 1 minute).
• Slow blink (1 second ON/1 second OFF repeated): The WAC2 is in pairing mode.
• Fast blink (250ms ON/250ms OFF repeated): The WAC2 is in process of removing
(unpairing) devices still in the construction area.
WaveLinx Area Controller G2 (WAC)
Description
www.cooperlighting.com