1-9
For terminal control please check the selector switiched for the analogue inputs.
Coding
Switch 1
OFF
OFF
ON
Also check the NPN, PNP selector switches for the digital inputs.
Test run the inverter
Test run the inverter from the keypad or the terminal control, checking all conditions are safe.
For advanced functions see the product manual.
To reset all paramaters to default values set F160 to = 1.
COMPLIANCE
A comprehensive guide to product compliance is available in the AC10 Product Manual.
Warning – Where there is a conflict between EMC and safety requirements personnel safety shall always
take precedence.
Operation of this equipment requires detailed installation and operation instructions provided in the product
manual intended for use on this product. This information is provided on the cd rom included in the container
this product was packaged in. It should be retained with the product at all times.
Caution: This is a product of the restricted sales distribution class according to IEC 61800-3. It is designated
as "professional equipment" as defined in EN61000-3. Permission of the supply authority shall be obtained
before connection to the low voltage supply.
In a domestic environment this product may cause radio interference in which case supplementary mitigation
measures may be required.
This equipment contains electrostatic discharge (ESD) sensitive parts. Observe static control precautions
when handling, installing and servicing this product.
EMC Emissions
Radiated Emissions comply with EN61800-3 category C1, C2 and C3 when installed in accordance with
instructions.
Conducted Emissions comply with EN61800-3 category C3 external filter.
Immunity complies with the requirement of EN61800-3, for equipment intended for use in the second
environment.
Planning Cable Runs
Use the shortest possible motor cable lengths.
Use a single length of cable to a star junction point to feed multiple motors.
Keep electrically noisy and sensitive cables apart. If this is not possible parallel cable runs should be
separated by at least 0.25metres, for runs longer than 10 meters, separation should be increased
proportionally.
Sensitive cables should cross noisy cables at 90
Never run sensitive cables close or parallel to the motor, dc link and braking chopper circuit for any distance.
Never run supply, dc link or motor cables in the same bundle as the signal/control and feedback cables, even
if they are screened.
Ensure EMC filter input and output cables are separately routed and do not couple across the filter.
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - info@sdsdrives.com
F203=2, channel AI2 is selected
SW1 coding switch
Coding
Analog Input AI2
Switch 2
signal
OFF
0~5V voltage
ON
0~10V voltage
ON
0~20mA current
F203=1, channel AI1 is selected
S1 toggle switch
+
0~10V voltage
o
angle.
English
-
-10~+10V voltage