Tipo RPE
11
Description
Electric heater type RPE 180 985.
- The heater is to:
- Maintain a minimum temperature in the body of a regulator in 'zero flow' to assist start up.
- Maintain a minimum temperature in the control circuit of a pressure regulator.
- Options:
- Electric pilot heater (with heating pot).
- Regulator bottom electric heater (without heating pot).
The temperature regulation is carried out through a relay, by a probe HAGER type EK083 and
through a multi-range thermostat HAGER type EK 186 set to maximum 60°C (or equivalent).
The thermowell of the RPE is constantly bathing in the non-flammable gas. Around the RPE, an
explosive atmosphere may occur, when:
- Opening of a valve,
- Opening of a vent,
- Leakage at a sealed connection.
If the sensor is switched off, the heating elements are switched off.
The RPE can operate in the absence of gas circulation.
The thermowell is be mounted vertically.
Rating: 230 VAC – 280 W- 50/60 Hz
The heater is fitted with a ¾ NPT flameproof cable gland.
12
Certificate history and evaluation reports
Issue
Date
Associated report
0
06 Apr 2018
R11598A/00
Note: Drawings that describe the equipment or component are listed in the Annex.
13
Conditions of manufacture
The following conditions are required of the manufacturing process for compliance with the
certification.
13.1
Where the product incorporates certified parts or safety critical components the
manufacturer shall ensure that any changes to those parts or components do not affect
the compliance of the certified product that is the subject of this certificate.
14
Special Conditions for Safe Use (Conditions of Certification)
None.
This certificate shall only be copied
in its entirety and without change
www.CMLEx.com
Webadmin.Regulators@emerson.com
Fisher.com
emerson Automation solutions
Américas
McKinney, Texas 75070 Estados Unidos
T +1 800 558 5853
+1 972 548 3574
Europa
Italia
Bolonia 40013,
T +39 051 419 0611
Francel SAS, 3 Avenue Victor Hugo,CS 80125, Chartres 28008, France
SIRET 552 068 637 00057 APE 2651B, N° TVA : FR84552068637, RCS Chartres B 552 068 637,
SAS capital 534 400 Euro
CML 18ATEX11081
Issue 0
Notes
Issue of prime certificate
2 of 2
Version: 7.0 Approval: Approved
Figura 7. Certificados de Examen (continuar)
Facebook.com/EmersonAutomationSolutions
LinkedIn.com/company/emerson-automation-solutions
Twitter.com/emr_automation
Asia
Singapur 128461, Singapur
T +65 6770 8337
Medio Oriente y África
Dubai, Emiratos Árabes Unidos
T +971 4 811 8100
Certificate Annex
Certificate Number
CML 18ATEX1081
Equipment
Electric heater Type RPE 180 985
Manufacturer
FRANCEL SAS [Brand name FISHER]
The following documents describe the equipment or component defined in this certificate:
Issue 0
Drawing No
Sheets
Rev.
Approved
date
DT 028
1 to 33
0
06 Apr 2018
142364
1 of 1
A
06 Apr 2018
142365
1 of 1
A
06 Apr 2018
ATEX-FA180985
1 of 1
-/-
06 Apr 2018
FA180985
1 of 1
BB
06 Apr 2018
D103706XFR2
1 to 4
-/-
06 Apr 2018
FA142388
1 to 3
CE
06 Apr 2018
1 of 1
This certificate shall only be copied
in its entirety and without change
www.CMLEx.com
D103694XES2 © 2017, 2018 Emerson Process Management Regulator
Technologies, Inc. Reservados todos los derechos. 05/18.
El logotipo de Emerson es una marca comercial y una marca de servicio
de Emerson Electric Co. Todas las demás marcas son propiedad
de sus respectivos dueños. Fisher™ es una marca de propiedad de
Fisher Controls International LLC, compañía de d'Emerson Automation
Solutions.
El contenido de esta publicación se presenta para usos informativos
solamente, y, aunque se ha hecho todo lo posible para garantizar su
exactitud, no debe interpretarse como garantías expresas o implícitas
respecto de los productos o servicios aquí descritos, ni de su uso
o aplicabilidad. Nos reservamos el derecho de modificar o mejorar
los diseños o las especificaciones de dichos productos en cualquier
momento y sin aviso previo.
Emerson Process Management Regulator Technologies, Inc., no asume
responsabilidad alguna por la selección, el uso ni el mantenimiento de
ningún producto. La responsabilidad por la debida selección, el uso y el
mantenimiento de cualquier producto de Emerson Process Management
Regulator Technologies, Inc., descansa exclusivamente en el comprador.
Title
DOCUMENTATION TECHNIQUE
DOIGT DE GANT
MAMELON REPRIS
RECHAUFFEUR ELECTRIQUE
RECHAUFFEUR ELECTRIQUE
NOTICE TECHNIQUE
IDENTIFICATION PLATE RPE INDEX
Version: 7.0 Approval: Approved