1. Safety Instructions
For skilled electricians and instructed
personnel in accordance with national
regulation, including the relevant standard and,
where applicable, in acc.with IEC 60079-17 on
electrical apparatus for explosive atmospheres.
¡The luminaires must not be operated in
Zones 0!
¡The tecnical data indicated on the
luminaires are to be observed!
¡Changes of the design and modifications to
the luminaires are not permitted!
¡The luminaires shall be operated as
intended and only in undamaged and
perfect conditions!
¡Only genuine Cooper Cr
Cooper Crouse-Hinds, S.A.
Cooper Cr
Cooper Cr
Cooper Cr
spare parts may be used for replacement!
¡Repairs that affect the explosion protection,
may only be carried out by
Cooper Cr
Cooper Cr
ouse-Hinds, S.A.
ouse-Hinds, S.A.
Cooper Cr
Cooper Cr
Cooper Crouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A. or a qualified
"electrician" and will subsequenctly have to
be cheked by an "expert"!
Do not keep these operating instructions
inside the luminaire during opertion.
¡The national safety rules and regulati-
ons for prevention of accidents and the
following safety instructions which are
marked with an (
) in theses operting
instructions, will have to be observed!
2. Conformity with standards
This explosion protected luminaires meets the
requeriment of IEC/EN 60079-1 and EN60598.
It also complies with the EC Directives
for"Apparatus and protective systems for use in
explosive atmospheres" (94/9/EC)
and "Electromagnetic compatibility" (89/336/EEC).
It has been designed, manufactured and tested in
accordance to the state of the art and according to
EN29001 (ISO9001).
The luminaire are suitables for use in explosive
atmospheres,Zone 1 and 2 acc. to IEC60079-10.
3. Technical data
Application
II2G
Class I:
Exd IIC
4)
Certificates:
LOM 02 ATEX2019X
Others, contact us
Serie of types:
See Table 1
Lamps to be use:
See Table 1
Lampholder
acc.EN 60061-2
Approval of the production
ATEX Quality assurance: LOM 02 ATEX 9040
Degree of protection
acc. EN60598:
IP 67
Insulation class
acc. EN60598:
I
Temperature of use:
-20
o
C to + 40
-20
o
C to + 55
Rated voltage
Luminaires without
Electromagnetic:
10%; 50Hz λ>0.90
Standard:
230V
+
On request:
220-230V;50/60Hz
198-254V; 50/60Hz λ>0.95
Electronic:
175-280 VDC
Material of enclosure:
Metal aloy aluminium
without Cu,painted
polyester grey.
Material of glass
Borosilicate
Storage temperature in
original Packing
-40
o
C a + 60
Notes:
3) Installed in areas without mechanical risk, due the nomal operation in the industrial processe.
4) See thermal class in table 2
Terminals capacity:
Entries of cables
Direct entry:
Dimensions:
4. Installation
¡The respective national regulations as well
as the general rules of engineering which apply
to the installation and operation of explosi-
on protected apparatus will have to be observed.
Transport and storage of the luminaire is permitted
in original packaging only!
¡Pay attention when mounting or repairing the
luminaire, dont damage the fire-finish of the glass
adquired during moulding (abrasions, sanding, etc.)
that can weaking their mechanical functions!
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
Number maximum to lamp with electronic ballats:
See table 6
Opening and closing the luminaires
¡The opening of luminaire always shall be
without voltage!
¡The luminaire is well closed when the cover is
completly threaded on the luminaire enclosure!
¡See secuency in figure 4!
Dimensions for mounting:
Accesories for mounting:
See
Cable entries
Mounting the selected cable entries
(cableglands or seals acc. needs) acc. type and
dimensions of the main conection cable, following
their manufacturer instructions.
¡The cable entries devices has to be a protection
mode than Exd IIC!
Unused cabe entries have to be closed by a
correspondante certified blanking plug Exd IIC.
If the original blanking plugs are used , these must
be tightened with 15 Nm torque.
Main conection:
Lamps mounting
¡Only must be mounting apropiated lamps
for the supplied luminaire. See indications in
the general label of the luminaire and in the present
instructions!
3)
5.
Taking into operation
¡Prior to operation check the luminaire for
its proper funtioning and installation in
compliance with these operting instructions and
others applicable regulations!
Only carry out insulation measurements between PE
and external conductor L1 (L1, L2, L3) as well as
o
C
between PE and N.
o
C
-
measurement voltage: max. 1kV AC/DC
- min. insulation: 2 MΩ
Then the luminaire have to be tightly closed.
o
C
2x2,5mm
2
PE ext.: 2 x 6mm
2
2 x ¾" ISO 7/1,
one plugged
See figure 3.
See figure 3
Cooper Cr
Cooper Crouse-Hinds, S.A.
Cooper Cr
ouse-Hinds, S.A. catalogue
ouse-Hinds, S.A.
ouse-Hinds, S.A.
Cooper Cr
Cooper Cr
ouse-Hinds, S.A.
See wiring diagram.
6.
Maintenance
¡Observe the national rules applicable to
maintenance, servicing, inspection and
repairing of apparatus for explosive atmospheres, as
well as the general rules of engineering!
Servicing
¡The responsable of the safe use of these
apparatus is the property!
When servicing, in particular those components that
affect the explosion protection , will have to cheked, e.g.:
Housing and glass for any cracks or damage.
The flameproof joint have to be clean,
undameged, without corrosion and perfect
greassed.
Gaskets for their perfect conditions.
Cable entries whitout corrosion.
Terminlas and blanking plugs for their firm fix.
Lamp replacement in acc. with the
manufacturer instructions.
Type of lamps used in acc. with the luminaire
specifications.
¡The flameproof of these apparatus have to
be greassed permanentlly in order to ensure it
protection in front of the corrosion, water ingrees
and seize-up problems. Cleaning rest of greasse and
corrosion no using sharp metallic devices who can
damage the surface of the joint, and greasing they
using apropiate greasse thermically and chemically
stable, like e.g.: Molikote
BR2 plus.
¡When the housing need to be repeinted, pay attention
that the flameproof joints rest without traks of
coating!
Inspection
¡The nationals regulations have to be
observed!
E.g. in Spain the inspections of the installations in
hazardous areas, have to be done by "qualified"
personnel in accordance with the Electrotechnical Low
Votage Regulation following the indications stablished
in IEC 60079-17.
¡When the inspections are in degree of
"Detailled" or "Closed", the luminaires have to
be disconnected from the main conection!
Repairing
¡The nationals regulations have to be
observed. The tasks of repairing have to be
made by "qualified" personnel!
¡The reparation of the sealed part between the
housing the glass have to be done by
Cooper Cr
Cooper Cr
Cooper Crouse-Hinds, S.A.
ouse-Hinds, S.A.!
ouse-Hinds, S.A.
ouse-Hinds, S.A.
Cooper Cr
Cooper Cr
ouse-Hinds, S.A.
¡ The users are not authorized to repair this sealed
part!
¡All reparations have to be done without voltage!
For repair electrical equipments in protection mode is
suggested follow the instructions indicated in
IEC 79-19.
¡Only use genuine
Cooper Cr
Cooper Cr
Cooper Cr
Cooper Cr
Cooper Crouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A. spare parts!
ouse-Hinds, S.A.
Subject to alteration or supplement of this product without
any advertisement before.
Cooper Crouse-Hinds, S.A.